Replacement part instructions – Franklin Fueling Systems Main System Board for Tank Sentinel, AutoStik, BulkStik ATGs User Manual
Page 2
Tank Sentinel
®
Replacement Part Instructions
0000200 REV C
E - m a i l : t e c h @ f r a n k l i n f u e l i n g . c o m F A X 1 - 2 0 7 - 2 8 2 - 9 0 0 2
T E L 1 - 8 0 0 - 9 8 4 - 6 2 6 6 P A G E
2 o f 4
s a l e s @ i n c o n . c o m
F A X 1 - 2 0 7 - 2 8 3 - 0 1 5 8
T E L 1 - 8 0 0 - 8 7 2 - 3 4 5 5
Need: Digital multimeter to read Voltage, screw drivers, and marking tape and pen.
Parts Supplied (Documents 000-0200, -0205, -0206, 0207, -0211, -0212, -0213) and:
1.) Main System Board (MSB) for Tank Sentinel, AutoStik Jr, BulkStik console (See Diagram A)
— o r —
2.) Main System Board (MSB) for the TS-2001, & AutoStik II (See Diagram B) and
3.) Packaging and Large Electronic Component anti-static bag (reuse to ship the old MSB
back to INCON... after receiving RMA paper work.)
Recommended:
Printout the complete System Setup Report and Tank Setup reports for all tanks (or up-load the
Setup configuration). Print this data before you proceed. You must cold boot and reprogram
the entire tank gauge after the MSB is replaced (the setup configuration reports down-load will
save a lot of the required time to reprogram a system console).
Removal & Installation Steps (with all Tank Gauge POWER OFF):
Removal of the old Main System Board
DANGER Electrical Shock Hazard. Locate and disconnect / turn off all external
power sources before working on or servicing these circuits (Relay Output terminals and
main system power terminals, and – in the case of TS-2001 consoles – the power
going to the TS-IEM module terminals).
1.)
Remove the golden metal probe & sensor terminal guard & power safety-shield.
2.)
Remove the external communication cables from the bottom of the console at:J9, J8 and J7.
3.)
Remove the external BriteBox Interface Cable at Connector at J11. Push the two side
tabs out, grasp the connector, and pull it out of its socket.
4.)
Verify that no voltage / power is present at the lower right set of vertically arranged
terminals ...check all terminals / circuits before removing any wires.
5.)
Tape and mark all wires at the lower right set of terminals so they can be correctly
reinstalled later.
6.)
Remove the tagged and marked power wires at the lower right side of the Main Circuit
Board (J13 TS-LLD, J14 INPUTS, J17 POWER & SAFETY GND, and J15 & J16
RELAY 1 & 2 OUTPUTS).
DO NOT remove the probe or sensor wires (this interface board will remain in place
because it is beneath, or at a lower level than the MSB.