beautypg.com

Voltage at test point vs. current (ma) – Cla-Val 393-01/3693-01 User Manual

Page 27

background image

LED

Function

Microprocessor

This LED is on when power is applied to the microprocessor, and

running

the microprocessor is running. If LED is not on, then verify power to the board,
as well as the SW1 setting on the top board

Actuator Increasing

This LED is on when the actuator is moving in the increasing direction

Actuator Decreasing

This LED is on when the actuator is mowing in the decreasing direction.

Fault

This LED will flash when a fault is present. The LED will flash at a
given rate. If the LED is flashing at 0.5 second intervals, then a LOS
for the remote setpoint is present. If the LED is flashing at 1 second
intervals, then a LOS for the process variable is present. If the LED
is flashing a 2 second intervals, then the remote operation is disabled
because the zero and span positions have not been set.

Red Enable Button

This LED will be on when the enable button and one of the other four
setup push buttons have been pressed at the same time

Minimum Position

This LED will be on when the actuator is at or below its set minimum position.

LS1 Position

This LED will be on when the process variable is at or below its minimum value.

LS2 Position

This LED will be on when the process variable is at or above its maximum value.

Maximum Position

This LED will be on when the actuator is at or above its maximum position.

Test Point

Function

Range

SPD

Speed of the actuator.

A value of 0 to 5 volts will be displayed.

See Figure #4

PSN

The position of the actuator.

A value of 4.49 to 1.57 volts will be displayed

4.49V is minimum and 1.57V is maximum position

CMD

The setpoint command.

If 4 to 20ma current is selected, 0.8 volts to 4 will

be displayed. If 0 to 5 volts, 0 to 10 or local setpoint

volts is selected, then 0 to 5 volts will be displayed.

PV

The process variable.

Input is 4 to 20ma only and a value 0.8 volts

to 4 volts will be displayed.

Tests using voltage meter.

There are four test points located on the logic board. The black test point labeled COM is used for the common
connection. Connect a voltage meter to the COM and the appropriate test point. The values of the four red test
points are shown in the following table:

Voltage at Test Point vs. Current (mA)

5.00

4.50

4.00

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

22.00

Curreent (mA)

Voltage at Test Point (V) vs Current (mA)

V

oltage at

T

est Point (V)

LED indication.
LEDs are provided to display the status of the actuator. They are located on the logic board. Their functions
are shown in the following table.

5