Warning/Alarm

Description

Cause

Remedy

59 — Current limit

The current is higher than

the value in 4–18 Current

Limit.

Ensure that motor data in

parameters 1–20 through

1–25 are set correctly.
Possibly increase the

current limit. Be sure that

the system can operate

safely at a higher limit.

60 — External interlock

A digital input signal is

indicating a fault condition

external to the frequency

controller.

62 — Output frequency at

maximum limit

The output frequency has

reached the value set in 4–

19 Max Output Frequency.

Check the application to

determine the cause.

Possibly increase the output

frequency. Be sure the

system can operate safely at

a higher output frequency.

The warning will clear wieh

the output drops below the

maximum limit.

65 — Control card over

temperature

The cut-out temperature of

the control card is 80°C.

Check that the ambient

operating temperature is

within limits.
Check for clogged filters.
Check fan operation.
Check the control card.

66 — Heatsink temperature

low

The frequency converter is

too cold to operate. This

warning is based on the

temperature sensor in the

IGBT module.

Increase the ambient

temperature of the unit.
A trickle amount of current

can be supplied to the

frequency controller

whenever the motor is

stopped by setting 2–00 DC

Hold/Preheat Current at 5%

and 1–80 Function at Stop.

67 — Option module

configuration has changed

One or more options have

either been added or

removed since the last

power down.

Check that the

configuration change is

intentional and reset the

frequency controller.

68 — Safe stop activated

Loss of the 24 VDC signal

on terminal 37 has caused

the frequency controller to

trip.

To resume normal

operation, apply 24 VDC to

terminal 37 and reset the

frequency controller.

69 — Power card

temperature

The temperature sensor on

the power card is either too

hot or too cold.

Check that the ambient

operating temperature is

within limits.
Check for clogged filters.
Check fan operation.
Check the power card.

70 — Illegal FC

configuration

The control card and power

card are incompatible.

Contact your supplier with

the typecode of the unit

from the

Troubleshooting