Warning/Alarm

Description

Cause

Remedy

27 — Brake chopper fault

The brake transistor is

monitored during

operation and if a short

circuit occurs, the brake

function is disabled and a

warning is issued.

The frequency converter is

still operational but, since

the brake transistor has

short-circuited, substantial

power is transmitted to the

brake resistor, even if it is

inactive.

Remove power to the

frequency converter and

remove the brake resistor.

28 — Brake check failed

The brake resistor is not

connected or not working.

Check 2–15 Brake Check.

29 — Heatsink temp

The maximum temperature

of the heatsink has been

exceeded. The temperature

fault will not reset until the

temperature falls below the

reset heatsink temperature.

The trip and reset points are

based on the frequency

converter power size.

Check for the following

conditions:

• Ambient temperature

too high.

• Motor cable too long.
• Incorrect airflow

clearance above and

below the frequency

converter.

• Blocked airflow

around the frequency

converter.

• Damaged heatsink

fan.

• Dirty heatsink.

30 — Motor phase U

missing

Motor phase U between the

frequency converter and the

motor is missing.

Remove power from the

frequency converter and

check motor phase U.

31 — Motor phase V missing Motor phase V between the

frequency converter and the

motor is missing.

Remove power from the

frequency converter and

check motor phase V.

32 — Motor phase W

missing

Motor phase W between

the frequency converter and

the motor is missing.

Remove power from the

frequency converter and

check motor phase W.

33 — Inrush fault

Too many power-ups have

occurred within a short time

period.

Let the unit cool to

operating temperature.

34 — Fieldbus

communication fault

Communication between

the fieldbus and the

communication option card

is not operating.

36 — Mains failure

This warning/alarm is only

active if the supply voltage

to the frequency converter

is lost and 14–10 Mains

Failure is NOT set to [0] No

Function.

Check the fuses to the

frequency converter and

mains power supply to the

unit.