Bell & Gossett P2001489 Integrated Technologic with Sensorless Control User Manual
Page 20

NOTICE:
Be sure to properly set the analog input configuration switches prior to using the analog
input.
Figure 9: Terminal connections for 4–20mA wired sensor
Figure 10: Terminal connections for 0–10V wired sensor
In order to set up the controller for closed loop control based on the feedback from an
external transducer, set the following parameters:
Table 4: Parameter settings for using a wired sensor for feedback
Parameter number
Description
Set to
0–10
Active Set-up
For wired pressure transducer select
Set-up 1. For wired flow transducer
select Set-up 2.
6-14*
Terminal 53 Low Ref./Feedb. Value
Minimum transducer feedback value.
For example, for a 0–40 psi DP
transducer, set to 0.
6-15*
Terminal 53 High Ref./Feedb. Value
Maximum transducer feedback value.
For example, for a 0–40 psi DP
transducer, set to 40.
6-17*
Terminal 53 Live Zero
Enabled
20-00
Feedback 1 Source
Analog Input 53*
20-12
Reference/Feedback
Select as appropriate for application.
For example, set to psi when using a
pressure transducer.
20–13
Minimum Reference/Feedback
Minimum transducer feedback value.
For example, for a 0–40 psi DP
transducer, set to 0 psi.
20–14
Maximum Reference/Feedback
Maximum trnasducer feedback value.
For example, for a 40 psi DP
transducer, set to 40 psi.
Electrical Installation
18
Integrated Technologic
®
with Sensorless Control INSTRUCTION MANUAL