NOTICE:
Be sure to properly set the analog input configuration switches prior to using the analog
input.

Figure 9: Terminal connections for 4–20mA wired sensor

Figure 10: Terminal connections for 0–10V wired sensor

In order to set up the controller for closed loop control based on the feedback from an
external transducer, set the following parameters:

Table 4: Parameter settings for using a wired sensor for feedback

Parameter number

Description

Set to

0–10

Active Set-up

For wired pressure transducer select

Set-up 1. For wired flow transducer

select Set-up 2.

6-14*

Terminal 53 Low Ref./Feedb. Value

Minimum transducer feedback value.

For example, for a 0–40 psi DP

transducer, set to 0.

6-15*

Terminal 53 High Ref./Feedb. Value

Maximum transducer feedback value.

For example, for a 0–40 psi DP

transducer, set to 40.

6-17*

Terminal 53 Live Zero

Enabled

20-00

Feedback 1 Source

Analog Input 53*

20-12

Reference/Feedback

Select as appropriate for application.

For example, set to psi when using a

pressure transducer.

20–13

Minimum Reference/Feedback

Minimum transducer feedback value.

For example, for a 0–40 psi DP

transducer, set to 0 psi.

20–14

Maximum Reference/Feedback

Maximum trnasducer feedback value.

For example, for a 40 psi DP

transducer, set to 40 psi.