Technical data – Xylem IM250R03 Aquavar CPC-FD User Manual
Page 28

28
500…600 Volt Fuses
500 … 600 Volt
Base
Drive
Frame
Size
Drive Input Fuse Ratings
Vendor
Part Number
HP
Identification
Amps
(600V)
Bussmann
Type
2
CPC5002xFD
R2
15
KTK-R-15
ACS550-PD-02A1-
6+N2000+X1555
3
CPC5004xFD
R2
15
KTK-R-15
ACS550-PD-04A1-
6+N2000+X1555
5
CPC5006xFD
R2
15
KTK-R-15
ACS550-PD-06A1-
6+N2000+X1555
7.5
CPC5009xFD
R2
15
KTK-R-15
ACS550-PD-09A1-
6+N2000+X1555
10
CPC5011xFD
R2
30
KTK-R-30
ACS550-PD-11A1-
6+N2000+X1555
15
CPC5017xFD
R2
30
KTK-R-30
ACS550-PD-17A1-
6+N2000+X1555
20
CPC5022xFD
R3
50
JJS-50
ACS550-PD-22A1-
6+N2000+X1555
25
CPC5027xFD
R3
50
JJS-50
ACS550-PD-27A1-
6+N2000+X1555
30
CPC5032xFD
R4
100
JJS-100
ACS550-PD-32A1-
6+N2000+X1555
40
CPC5041xFD
R4
100
JJS-100
ACS550-PD-41A1-
6+N2000+X1555
50
CPC5052xFD
R4
100
JJS-100
ACS550-PD-52A1-
6+N2000+X1555
60
CPC5062xFD
R4
100
JJS-100
ACS550-PD-62A1-
6+N2000+X1555
75
CPC5077xFD
R6
125
170M1368
ACS550-PD-77A1-
6+N2000+X1555
100
CPC5099xFD
R6
125
170M1368
ACS550-PD-99A1-
6+N2000+X1555
125
CPC5125xFD
R6
160
170M1369
ACS550-PD-125A1-
6+N2000+X1555
150
CPC5144xFD
R6
200
170M1370
ACS550-PD-144A1-
6+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.
Input Power Cables / Wiring – R7/R8
NEC
Based on:
• NEC Table 310-16 for copper wires
• 40 °C (104 °F) ambient temperature
• 90 °C (194 °F) wire insulation
• Copper cables with concentric copper shield
• Not more than three current-carrying conductors in raceway or cable, or earth (directly buried).
Max Load Current (A) Cu Wire Size (AWG/kcmil)
Max Load Current (A) Cu Wire Size (AWG/kcmil)
345
400 MCM or 2 x 2/0
474
2 x 250
391
500 MCM or 2 x 3/0
534
2 x 300
410
2 x 3/0
615
2 x 350
465
2 x 4/0
711
2 x 500
TECHNICAL DATA