CABLE SIZING/ RATINGS
380…480 Volt Drives
GWT AQUAVAR CPC
Volt-
age Phase
NEMA 1
Base
Model
Cont.
Output
Amps
Normal
Duty
Horsepower
Frame
Size²
Output Cable
Min. AWG¹
Input Cable
Min. AWG¹
Vendor
Part Number
460
3
CPC40061
6.9
3
R1
14
14
ACS550-U1-06A9-
4+N2000+P918+X1555
CPC40081
8.8
5
R1
14
14
ACS550-U1-08A8-
4+N2000+X1555
CPC40121
11.9
7.5
R1
14
14
ACS550-U1-012A-
4+N2000+P918+X1555
CPC40151
15.4
10
R2
12
14
ACS550-U1-015A-
4+N2000+X1555
CPC40231
23
15
R2
12
10
ACS550-U1-023A-
4+N2000+X1555
CPC40311
31
20
R3
10
8
ACS550-U1-031A-
4+N2000+X1555
CPC40381
38
25
R3
8
8
ACS550-U1-038A-
4+N2000+X1555
CPC40441
44
30
R4
8
6
ACS550-U1-045A-
4+N2000+X1555
CPC40591
59
40
R4
6
4
ACS550-U1-059A-
4+N2000+X1555
CPC40721
72
50
R4
4
3
ACS550-U1-072A-
4+N2000+X1555
CPC40771
77
60
R5
4
3
ACS550-U1-078A-
4+N2000+X1555
CPC40961
96
75
R5
3
1
ACS550-U1-097A-
4+N2000+X1555
CPC41241
124
100
R6
1
1/0
ACS550-U1-125A-
4+N2000+X1555
CPC41571
157
125
R6
2/0
3/0
ACS550-U1-157A-
4+N2000+X1555
CPC41801
180
150
R6
3/0
4/0
ACS550-U1-180A-
4+N2000+X1555
CPC42451
245
200
R7
300MCM or
2 X 1/0
350MCM or
2 X 2/0
ACS550-U1-246A-
4+N2000+X1555
CPC43161
316
250
R7
500MCM or
2 X 3/0
2 X 3/0
ACS550-PC-316A-
4+N2000+X1555
CPC43681
368
300
R8
600MCM or 2 X
4/0 or 3 X 1/0
2 X 4/0
ACS550-PC-368A-
4+N2000+X1555
CPC44141
414
350
R8
2 X 250MCM
or 3 X 2/0
2 X 300MCM
ACS550-PC-414A-
4+N2000+X1555
CPC44861
486
400
R8
2 X 300MCM
or 3 X 3/0
2 X 350MCM
ACS550-PC-486A-
4+N2000+X1555
CPC45261
526
450
R8
2 X 350MCM
or 3 X 4/0
2 X 500MCM
ACS550-U2-526A-
4+N2000+X1555
CPC46021
602
500
R8
2 X 500MCM or
3 X 250MCM
2 X 500MCM or
3 X 250MCM
ACS550-U2-602A-
4+N2000+X1555
CPC46451
645
550
R8
2 X 500MCM or
3 X 250MCM
2 X 500MCM or
3 X 250MCM
ACS550-U2-645A-
4+N2000+X1555
NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local, state or NEC codes.
NOTE 2: Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult technical
section ( CABLE TERMINALS) for max. wire diameter and torque values. For submersible motors consult motor manufacturer
on recommended wire type and size based on lead length and amperage.
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended wire sizing for the input and output cables.
NOTE:
THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.