FUSE SIZING/ RATINGS
380…480 Volt Drives
GWT AQUAVAR CPC
Voltage Phase
NEMA 1
Base
Model
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size
Input
Current
Amps
Fuse Type³
JJS
Vendor
Part Number
460
3
CPC40061
6.9
3
R1
7.9
10
ACS550-U1-06A9-
4+N2000+P918+X1555
CPC40081
8.8
5
R1
10.1
15
ACS550-U1-08A8-
4+N2000+X1555
CPC40121
11.9
7.5
R1
13.7
15
ACS550-U1-012A-
4+N2000+P918+X1555
CPC40151
15.4
10
R2
17.7
20
ACS550-U1-015A-
4+N2000+X1555
CPC40231
23
15
R2
26.5
30
ACS550-U1-023A-
4+N2000+X1555
CPC40311
31
20
R3
35.7
40
ACS550-U1-031A-
4+N2000+X1555
CPC40381
38
25
R3
43.7
50
ACS550-U1-038A-
4+N2000+X1555
CPC40441
44
30
R4
50.6
60
ACS550-U1-045A-
4+N2000+X1555
CPC40591
59
40
R4
67.9
80
ACS550-U1-059A-
4+N2000+X1555
CPC40721
72
50
R4
82.8
90
ACS550-U1-072A-
4+N2000+X1555
CPC40771
77
60
R5
88.6
100
ACS550-U1-078A-
4+N2000+X1555
CPC40961
96
75
R5
110.4
125
ACS550-U1-097A-
4+N2000+X1555
CPC41241
124
100
R6
142.6
175
ACS550-U1-125A-
4+N2000+X1555
CPC41571
157
125
R6
180.6
200
ACS550-U1-157A-
4+N2000+X1555
CPC41801
180
150
R6
207.0
250
ACS550-U1-180A-
4+N2000+X1555
CPC42451
245
200
R7
281.8
300
ACS550-U1-246A-
4+N2000+X1555
CPC43161
316
250
R7
363.4
400
ACS550-PC-316A-
4+N2000+X1555
CPC43681
368
300
R8
423.2
450
ACS550-PC-368A-
4+N2000+X1555
CPC44141
414
350
R8
476.1
500
ACS550-PC-414A-
4+N2000+X1555
CPC44861
486
400
R8
558.9
600
ACS550-PC-486A-
4+N2000+X1555
CPC45261
526
450
R8
604.9
600
ACS550-U2-526A-
4+N2000+X1555
CPC46021
602
500
R8
692.3
800
ACS550-U2-602A-
4+N2000+X1555
CPC46451
645
550
R8
741.8
800
ACS550-U2-645A-
4+N2000+X1555
NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type and JJS are
shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes.
NOTE: