CABLE SIZING/ RATINGS
208…240 Volt Drives
GWT AQUAVAR CPC
Voltage Phase
NEMA 1
Base
Model
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size²
Output
Cable
Min. AWG¹
Input
Cable
Min. AWG¹
Vendor
Part Number
230
1
CPC20171
8.5
2
R1
14
14
ACS550-U1-017A-
2+N2000+P918+X1555
CPC20241
12
3
R2
14
10
ACS550-U1-024A-
2+N2000+X1555
CPC20311
15.5
5
R2
14
8
ACS550-U1-031A-
2+N2000+X1555
CPC20461
23
7.5
R3
12
6
ACS550-U1-046A-
2+N2000+X1555
CPC20591
29.5
10
R3
10
4
ACS550-U1-059A-
2+N2000+X1555
CPC20881
44.0
15
R4
8
2
ACS550-U1-088A-
2+N2000+X1555
CPC21141
57.0
20
R4
6
1/0
ACS550-U1-114A-
2+N2000+X1555
CPC21431
71.5
25
R6
4
3/0
ACS550-U1-143A-
2+N2000+X1555
CPC21781
89.0
30
R6
3
4/0
ACS550-U1-178A-
2+N2000+X1555
CPC22211
110.5
40
R6
2
300 MCM
or 2 x 1/0
ACS550-U1-221A-
2+N2000+X1555
CPC22481
124.0
50
R6
1
350MCM
or 2 x 2/0
ACS550-U1-248A-
2+N2000+X1555
3
CPC20121
11.8
3
R1
14
14
ACS550-U1-012A-
2+N2000+P918+X1555
CPC20171
16.7
5
R1
14
14
ACS550-U1-017A-
2+N2000+P918+X1555
CPC20241
24.2
7.5
R2
12
10
ACS550-U1-024A-
2+N2000+X1555
CPC20311
30.8
10
R2
10
8
ACS550-U1-031A-
2+N2000+X1555
CPC20461
46.2
15
R3
8
6
ACS550-U1-046A-
2+N2000+X1555
CPC20591
59.4
20
R3
6
4
ACS550-U1-059A-
2+N2000+X1555
CPC20751
74.8
25
R4
4
3
ACS550-U1-075A-
2+N2000+X1555
CPC20881
88.0
30
R4
3
2
ACS550-U1-088A-
2+N2000+X1555
CPC21141
114.0
40
R4
2
1/0
ACS550-U1-114A-
2+N2000+X1555
CPC21431
143.0
50
R6
1/0
3/0
ACS550-U1-143A-
2+N2000+X1555
CPC21781
178.0
60
R6
2/0
4/0
ACS550-U1-178A-
2+N2000+X1555
CPC22211
221.0
75
R6
4/0
300 MCM
or 2 x 1/0
ACS550-U1-221A-
2+N2000+X1555
CPC22481
248.0
100
R6
250MCM
or 2 X 1
350MCM
or 2 x 2/0
ACS550-U1-248A-
2+N2000+X1555
NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local, state or NEC codes.
NOTE 2: Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult technical
section ( CABLE TERMINALS)
TECHNICAL DATA
The following tables provide current, horsepower, frame size and recommended cable sizes for the Aquavar CPC.
NOTE:
THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.