CABLE SIZING/ RATINGS

600 Volt Drives

GWT AQUAVAR CPC

Voltage Phase

NEMA 1

Base

Model

Cont.

Output

Amps

Normal Duty

Horsepower

Frame

Size²

Output

Cable

Min. AWG¹

Input

Cable

Min. AWG¹

Vendor

Part Number

460

3

CPC50031

2.7

2

R2

14

14

ACS550-U1-02A7-

6+N2000+X1555

CPC50041

3.9

3

R2

14

14

ACS550-U1-03A9-

6+N2000+X1555

CPC50061

6.1

5

R2

14

14

ACS550-U1-06A1-

6+N2000+X1555

CPC50091

9

7.5

R2

14

14

ACS550-U1-09A0-6

+N2000+X1555

CPC50111

11

10

R2

14

14

ACS550-U1-011A-

6+N2000+X1555

CPC50171

17

15

R2

14

14

ACS550-U1-017A-

6+N2000+X1555

CPC50221

22

20

R3

12

10

ACS550-U1-022A-

6+N2000+X1555

CPC50271

27

25

R3

10

10

ACS550-U1-027A-

6+N2000+X1555

CPC50321

32

30

R4

10

8

ACS550-U1-032A-

6+N2000+X1555

CPC50411

41

40

R4

8

6

ACS550-U1-041A-

6+N2000+X1555

CPC50521

52

50

R4

6

6

ACS550-U1-052A-

6+N2000+X1555

CPC50621

62

60

R4

6

4

ACS550-U1-062A-

6+N2000+X1555

CPC50771

77

75

R6

4

3

ACS550-U1-077A-

6+N2000+X1555

CPC50991

99

100

R6

3

1

ACS550-U1-099A-

6+N2000+X1555

CPC51251

125

125

R6

2

2/0

ACS550-U1-125A-

6+N2000+X1555

CPC51441

144

150

R6

1

3/0

ACS550-U1-144A-

6+N2000+X1555

NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local or Provincial codes.
NOTE 2: Terminal block for input voltage and output motor voltage have diameter limits. Consult technical section ( CABLE
TERMINALS) for max. wire diameter and torque values.

For submersible motor applications refer to motor manufacturers recommendations based on lead length and voltage drop.

TECHNICAL DATA

The following tables provide current, horsepower, frame size and recommended cable sizes for the Aquavar CPC.

NOTE:

THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.