7 TABLES
Table 1. Equipment Weight
Weight - Lbs
Component
Empty
Packed**
Installed**
Battery Cabinet – 27”
420
1600-3400
1500-3300
Battery Cabinet – 44”
550
1730-3530
1630-3430
Transition Cabinet
350
450
**Packed & Installed weight of the battery cabinet varies based on the make and model of the battery used.
Table 2. Battery Cabinet Clearances
From Top of Cabinet
18” for ventilation
From Front of Cabinet
36” working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
Table 3. Maximum cable size
kVA
Rectifier Input
Bypass Input
DC Input
Output (Load)
Ground
10
#3 AWG
#3 AWG
#3 AWG
#3 AWG
#3 AWG
20
#3 AWG
#3 AWG
#3 AWG
#3 AWG
#3 AWG
30
#1 AWG
#1 AWG
#1 AWG
#1 AWG
#1 AWG
40
#1 AWG
#1 AWG
#1 AWG
#1 AWG
#1 AWG
50
#4/0 AWG
#4/0 AWG
#4/0 AWG
#4/0 AWG
#4/0 AWG
80
#4/0 AWG
#4/0 AWG
#4/0 AWG
#4/0 AWG
#4/0 AWG
100
500 MCM
500 MCM
500 MCM
500 MCM
350 MCM
120
500 MCM
500 MCM
500 MCM
500 MCM
350 MCM
150
500 MCM
500 MCM
500 MCM
500 MCM
350 MCM
225
2x500 MCM
2x500 MCM
2x750 MCM
2x500 MCM
350 MCM
300
2x750 MCM
2x500 MCM
2x750 MCM
2x500 MCM
350 MCM
400
4x500 MCM
2x500 MCM
4x600 MCM
2x500 MCM
350 MCM
500
4x500 MCM
2x500 MCM
4x600 MCM
2x500 MCM
350 MCM
750
5x500 MCM
4x500 MCM
6x600 MCM
4x500 MCM
4x500 MCM