2 operation modes, Operation modes – GE Industrial Solutions LP33 Series 80 & 100 User Manual User Manual
Page 13

Modifications reserved
Page 13/66
OPM_LPS_3UO_80K_M10_1US_V010.doc
User Manual LP33 Series 80 & 100 UL S1
4.2 OPERATION MODES
 
This section describes the different possible operation modes of the UPS explaining the function of the 
main modules of the UPS. 
 
 
VFI (Voltage Frequency Independent) Mode operation
Under normal conditions the load is permanently 
powered by the inverter with constant amplitude 
and frequency. 
 
The rectifier, powered by the mains, supplies the 
inverter and the battery-charger keeps the 
battery fully charged. 
Fig. 4.2-1 Energy flow in VFI Mode operation
The inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and 
frequency independently from the input mains power. 
 
 
 
 
ECO Mode operation 
 
When the ECO Mode is selected, and the mains 
power is available, the load is normally powered 
through the automatic bypass. 
 
When the mains voltage is detected out of the 
prescribed tolerances, the load is automatically 
transferred to the inverter. 
 
When the mains recovers, the load returns to the 
automatic bypass after a variable time defined 
by the control unit. 
Fig. 4.2-2 Energy flow in ECO Mode operation
The ECO Mode can be configured directly by the user for higher efficiency, considering the mains 
reliability and criticality of the load. 
 
The selection between the two operation modes “VFI Mode and ECO Mode”, or switching between 
operation modes at required time, can be done through the UPS control panel (see Section 7.1.3). 
 
 
In case of parallel system
 
ECO Mode cannot be enabled for RPA Parallel System. 
Attention: 
A single unit equipped with a RPA - Parallel board, must be considered as parallel, thus 
disabling ECO Mode. 
 
 
