beautypg.com

GE Industrial Solutions EntelliGuard E Bell Alarm with Lockout for 800–2000 Ampere User Manual

Entelliguard™ power circuit breaker accessories, Introduction, Operation

background image

Introduction

The Bell Alarm with Lockout prevents closing of the
breaker after a protection trip until the accessory is reset.
It contains a set of switch contacts to remotely indicate
that the circuit breaker has opened due to a protection
trip.

The catalog number for the Bell Alarm with Lockout kit
for 800–2000 ampere EntelliGuard breakers is
EGBLALMSFKIT. The kit includes the Bell Alarm
module, a universal mounting plate, and all necessary
hardware for installation.

Operation

The Bell Alarm with Lockout is activated and its status
circuit changes state whenever the EntelliGuard
Messenger™ trips the breaker due to an overcurrent,
ground fault, or protective relay function. A trip caused by
the manual

OPEN

button or the Shunt Trip does not

activate the Bell Alarm with Lockout. The EntelliGuard
Messenger continuously monitors the state of the status
circuit.

The Bell Alarm with Lockout can be reset by manually
depressing the target on the breaker escutcheon. This will
return the Bell Alarm with Lockout status contact to its
normal position and allow the breaker to be closed. The
connections of the Bell Alarm with Lockout to the
secondary disconnect are illustrated in Figure 1.

Note that the circuit breaker must be racked in to the
connected position, as indicated by the legend

CONN

on

the draw-out position indicator flag, for proper operation
of the lockout function of a Bell Alarm with Lockout.

Figure 1. Bell Alarm with Lockout connections to the secondary

disconnect.

Installation

WARNING: Before installing any accessories,
turn the breaker

OFF

, disconnect it from all

voltage sources, and discharge the closing
springs.

AVERTISSEMENT: Tourner le disjoncteur à
la position

OFF

, le débrancher de toute source

de tension et décharger les ressorts de
fermeture avant l’installation de tout
accessoire.

The following installation procedure is described in
several sections. First, follow the procedure for preparing
the breaker for installation. Next, install the Bell Alarm
with Lockout, then return the breaker to operation.

Preparing for Installation

1. Open the breaker and remove it from the cubicle or

substructure. (See DEH201 or DEH203 for detailed
instructions.)

2. Insert the racking handle (catalog number

568B731G1 or G2) and move the racking mechanism
to the

DISC

position, as shown on the draw-out posi-

tion indicator.

3. Remove the trim ring from the around the breaker

escutcheon by disengaging the ends of the spring-
loaded rods from the escutcheon brackets.

4. Remove the six screws securing the escutcheon to the

breaker. Pull the manual charging handle out part
way, then slide off the escutcheon.

Installing the Bell Alarm with Lockout

5. Screw the three standoffs into the front plate of the

breaker, as illustrated in Figure 2.

6. Place the Bell Alarm mounting plate over the

standoffs and secure it with the supplied washers and
nuts. Ensure that the actuating tab from the breaker

g

EntelliGuard™ Power Circuit Breaker
Accessories

Bell Alarm with Lockout for 800–2000 Ampere

Circuit Breakers

DEH238 Installation Instructions R02