Rating Plugs & Ground Fault Sensors
Following the instructions supplied with the rating plugs and
Ground Fault sensors, illustrated in Figure 2.A & 2.B, install the
plug into the breaker body. Available rating plugs, with their
catalog numbers, are listed in Table 4.A ,4.B.,4.C & 5.
Figure 2.A. Record Plus Fixed & Adjustable rating plug.
Figure 2.B. Ground Fault sensor
.
Catalog Number
Sensor Rating, A
Plug Rating, A
FGRP3K0125
250
125
FGRP3K0150
150
FGRP3K0175
175
FGRP3K0200
200
FGRP3K0225
225
FGRP3K0250
250
FGRP3L0175
400
175
FGRP3L0200
200
FGRP3L0225
225
FGRP3L0250
250
FGRP3L0300
300
FGRP3L0350
350
FGRP3L0400
400
FGRP3M0300
600
300
FGRP3M0350
350
FGRP3M0400
400
FGRP3M0450
450
FGRP3M0500
500
FGRP3M0600
600
Table 4.A. Rating plug catalog numbers and ratings for SMR1.
Catalog Adjustable Sensor
Rating
Plug Rating
FGRN3K0160 Adjustable
250A
G400
FGRN3K0250 Adjustable
G400
FGRN3L0250 Adjustable
400A
G400
FGRN3L0400 Adjustable
G400
FGRN3M0600 Adjustable
600A
G600
FGRN2K0160 Adjustable
250A
G400
FGRN2K0250 Adjustable
G400
FGRN2L0250 Adjustable
400A
G400
FGRN2L0400 Adjustable
G400
FGRN2M0600 Adjustable
600A
G600
Table 4.B. Adjustable Rating plug catalog numbers and
ratings for SMR2.
Table 4.C. Fixed Rating plug catalog numbers and ratings
for SMR2.
Table 5. Ground Fault sensors.
Catalog Fixed
Sensor
Rating
Plug
Rating
FGRM3K0100 Fixed
250A
100
FGRM3K0110 Fixed
110
FGRM3K0125 Fixed
125
FGRM3K0150 Fixed
150
FGRM3K0160 Fixed
160
FGRM3K0175 Fixed
175
FGRM3K0200 Fixed
200
FGRM3K0225 Fixed
225
FGRM3K0250 Fixed
250
FGRM3L0175 Fixed
400A
175
FGRM3L0200 Fixed
200
FGRM3L0225 Fixed
225
FGRM3L0250 Fixed
250
FGRM3L0300 Fixed
300
FGRM3L0350 Fixed
350
FGRM3L0400 Fixed
400
FGRM3M0300 Fixed
600A
300
FGRM3M0350 Fixed
350
FGRM3M0400 Fixed
400
FGRM3M0450 Fixed
450
FGRM3M0500 Fixed
500
FGRM3M0600 Fixed
600
FGRM2K0100 Fixed
250A
100
FGRM2K0110 Fixed
110
FGRM2K0125 Fixed
125
FGRM2K0150 Fixed
150
FGRM2K0160 Fixed
160
FGRM2K0175 Fixed
175
FGRM2K0200 Fixed
200
FGRM2K0225 Fixed
225
FGRM2K0250 Fixed
250
FGRM2L0175 Fixed
400A
175
FGRM2L0200 Fixed
200
FGRM2L0225 Fixed
225
FGRM2L0250 Fixed
250
FGRM2L0300 Fixed
300
FGRM2L0350 Fixed
350
FGRM2L0400 Fixed
400
FGRM2M0300 Fixed
600A
300
FGRM2M0350 Fixed
350
FGRM2M0400 Fixed
400
FGRM2M0450 Fixed
450
FGRM2M0500 Fixed
500
FGRM2M0600 Fixed
600
Catalog
Number
Amps Type
FGGS0250 250
Ground Fault SMR2
Sensor 250A
FGGS0400 400
Ground Fault SMR2
Sensor 400A
FGGS0600 600
Ground Fault SMR2
Sensor 600A