Car2548dc series dc-dc converters, Data sheet, Feature specifications (continued) – GE Industrial Solutions CAR2548DC series User Manual
Page 5: Digital interface specifications

GE
Data Sheet
CAR2548DC series dc-dc converters
Input: -36Vdc to -75Vdc; Output: 48Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A
December 6, 2013
©2013 General Electric Company. All rights reserved.
Page 5
Feature Specifications (continued)
Parameter
Symbol
Min
Typ
Max
Unit
SMBAlert# (Interrupt) (Needs to be pulled HI via an external
i t )
Logic High (No Alert - normal)
I
OH
20 µA
V
OH
0.7V
DD
12 V
DC
Logic Low (Alert is set)
I
OL
20 mA
V
OL
0
0.4 V
DC
Output current monitor (Imon)
Resolution
100
mV/A
Accuracy
-5 5 %
of
FL
Measurement range
I
o
0 52
A
DC
Analog output range
V
mon
0 5.2
V
DC
Sourced output current
5 mA
DC
Digital Interface Specifications
Parameter
Conditions
Symbol
Min
Typ
Max
Unit
PMBus Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)
V
IH
2.1 3.6 V
DC
Input Logic Low Voltage (CLK, DATA)
V
IL
0 0.8 V
DC
Input high sourced current (CLK, DATA)
I
IH
0 10 μA
Output Low sink Voltage (CLK, DATA, SMBALERT#)
I
OUT
=3.5mA V
OL
0.4 V
DC
Output Low sink current (CLK, DATA, SMBALERT#)
I
OL
3.5
mA
Output High open drain leakage current
(CLK,DATA, SMBALERT#)
V
OUT
=3.6V I
OH
0 10 μA
PMBus Operating frequency range
Slave Mode
F
PMB
10 400 kHz
Measurement System Characteristics
Clock stretching
t
STRETCH
25 ms
I
OUT
measurement range
Linear
I
RNG
0 52 A
DC
I
OUT
measurement accuracy 25°C
I
ACC
-3
+3
% of FL
V
OUT
measurement range
Linear
V
OUT(rng)
0
60
V
DC
V
OUT
measurement accuracy
V
OUT(acc)
-3 +3 %
Temp measurement range
Linear
Temp
(rng)
0
120
C
Temp measurement accuracy
6
Temp
(acc)
-5 +5
C
I
IN
measurement range
Linear
I
IN(rng)
0 80 A
DC
I
IN
measurement accuracy
I
IN(acc)
-5 +5 %
V
IN
measurement range
Linear
V
IN(rng)
0
80 V
DC
V
IN
measurement accuracy
V
IN(acc)
-3 +3 %
P
IN
measurement range
Linear
P
N(rng)
0 3000 W
P
IN
measurement accuracy
P
IN(acc)
-5 +5 %
Fan Speed measurement range
Linear
0
30k
RPM
Fan Speed measurement accuracy
-5
5
%
Fan speed control range
-direct-
0
100
%
6
Temperature accuracy reduces non-linearly with decreasing temperature