4–4 high-current testing – GE Industrial Solutions ProTrip Trip Units for Low-Voltage User Manual
Page 16

ProTrip™ Trip Units
Chapter 4. Maintenance and Trouble-Shooting
10
Figure 14. Removing the target module.
Target Module Battery Replacement
To replace the two batteries in the Target Module, remove
the module from the Trip Unit as described above. Slide
the old batteries out from the battery compartment at the
rear of the Target Module. It may help to carefully pry
them out with a small screwdriver blade in the cutout on
top of the module. Slide the new batteries into the battery
compartment. Be careful not to short out the batteries
during removal or installation. Recommended
replacement batteries are Panasonic CR1616, Eveready E-
CR1616BP, and Duracell DC1616B.
WARNING: Replace the batteries with Panasonic
CR1616, Eveready E-CR1616BP, or Duracell DC1616B
only. Use of a different battery may present risk of fire,
explosion, or damage to equipment. Observe proper
battery polarity when installing in the battery
compartment.
AVERTISSEMENT: Remplacer la batterie avec
uniquement des Panasonic CR1616, Eveready E-
CR1616BP, ou Duracell DC1616B. L’utilisation d’autres
batteries peut présenter un risque de feu, d’explosion ou
d’endommagement du matériel. Respecter la polarité de
la batterie en l’installant dans son logement.
WARNING: The batteries may explode if mistreated. Do
not recharge, disassemble, or dispose of in fire. Keep the
battery away from children and dispose of the used
battery promptly.
AVERTISSEMENT: La batterie peut exploser en cas de
mauvaise utilisation. Ne pas la recharger, l’ouvrir ou la
jeter dans un feu. Doit être garder hors de portée des
enfants. Une fois usée, la batterie doit être jeté
rapidement.
4–4 High-Current Testing
The TVRMS2 Test Kit does not defeat ground fault on the
ProTrip Trip Unit. If the breaker equipped with a ProTrip
Trip Unit is undergoing high-current testing, then two
poles must be connected in series to prevent ground fault
operation.