GE Industrial Solutions CR454A Series Starters User Manual
Definite purpose contactors & starters
Definite Purpose
Contactors & Starters
CR453A Series Contactors
CR454A Series Starters
Description
GE’s CR453A magnetic contactors provide a 2- or 3-pole
device for use in air conditioning units or other general
purpose applications. These instructions give information
about ratings, installation, accessories and wiring, overload
relay may be added if needed. Factory assembled starters
CR454A include overload relay
.
Motor branch circuit and control circuit overcurrent
protection should be supplied in accordance with the
National Electrical Code or local code as required. CR453A
contactors are suitable for use on a circuit capable of
delivering not more than 5,000 RMS symmetrical amperes,
600 volts maximum when protected by fuses or a circuit
breaker having an interrupting rating not less than 5,000
RMS symmetrical amperes.
Use 75° C copper conductors only.
Ratings – Full Voltage, Non-Reversing
Frame
Ratings
Resistive
Size
VAC
FLA
LRA
Horsepower
Rating Per
1 PH
3 PH
Pole
120
150
2
–
CR453AB
240
25
150
3
7.5
35
480
125
–
10
600
100
–
10
120
180
2
–
CR453AC
240
30
180
5
10
40
480
150
–
15
600
120
–
15
120
240
3
–
CR453AD
240
40
240
7.5
10
50
480
200
–
20
600
160
–
20
Caution: Before installing in a nuclear application, determine that the product is intended for such use.
Warning: Disconnect power before installing or servicing.
Typical CR453A Series contactor
Power Terminal Tightening Torque (lbs.-in.)
Terminal Type
Torque Values
Box Lug
40
Pressure Plate
20
Binding Screw
20