Car1248fp series rectifier, Data sheet, Input: 90v – GE Industrial Solutions CAR1248FP series User Manual
Page 9: Output: 48v, Leds, I/o expander option, Alarm table, Connector

GE
Data Sheet
CAR1248FP series rectifier
Input: 90V
AC
to 264V
AC
; Output: 48V
DC
@ 1200W; 5 V
DC
@ 0.5A
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 9
LEDs
Three LEDs are located on the front faceplate. The AC_OK LED
provides visual indication of the INPUT signal function. When
the LED is ON GREEN the power supply input is within normal
design limits.
When the DC_OK LED is GREEN the DC output is present.
When the FAULT_LED is RED then a fault condition exists and
the power supply may not provide output power. The table
below further defines these states:
I/O Expander option
The CAR1248FPx without extended i2c communications (blank
under the software option) has a single status/control byte I/O
expander that is accessible via address 0 x 4Eh (A2, A1, A0 are
pilled HI). This byte takes the form;
7
6
5
4
3
2
1
0
n/s n/s Fault ON/OFF Temp_OK n/s DCOK ACOK
n/s – not supported
Bits 0, 1, 3, and 5 are ‘read_only’ and are HI [1] during normal
operation. The rectifier needs to be biased externally in order to ‘read’
its operational state without the presence of input power.
Bit 4 is a ‘read/write’ bit that can be used to verify the ON/OFF
commanded state or change the commanded output of the rectifier.
In order to turn the output OFF this bit needs to be pulled LO [0].
No PEC support is provided. Standard i
2
c commands apply.
Alarm Table
Test Condition
LED Indicator
Monitoring Signals
AC OK
DC OK
FAULT
FAULT
DC OK
AC OK
TEMP OK
1 Normal
Operation
Green
Green
OFF High High High
High
2
Low or NO INPUT
OFF
OFF
OFF
Low Low Low High
3 OVP
Green
OFF
Red
Low Low High High
4 Over
Current
Green
OFF
Red
High Low High High
5
Over Temp Fault
Green
OFF
Red
Low Low High Low
Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no AC.
Connector
FCI Berg P/N: 51939-070
Mating connector: FCI Berg P/N: 51915-050
Pin
Function
Pin
Function
Pin
Function
Pin
Function
A1 Vstb
B1 Fault C1 ISHARE
D1 VProg
A2
Vstb Return
B2
I Monitor (IMON)
C2
N/C
D2
OVP Test Point
A3
Signal Return
B3
Enable: “0” –ON “1” -OFF
C3
Over Temp Warning
D3
Remote ON/OFF
A4
Write Protect (WP)
B4
PS Present
C4
I
2
C Address (A0)
D4
DC OK
A5
Remote Sense (+)
B5
SDA (I
2
C bus)
C5
I
2
C Address (A1)
D5
AC OK
A6
Remote Sense (-)
B6
SCL (I
2
C bus)
C6
I
2
C Address (A2)
D6
Interrupt
P1 Line P2
Neutral P3 Chassis
P4 +V
OUT
P5
Output
Return