Car1248fp series rectifier, Data sheet, Input: 90v – GE Industrial Solutions CAR1248FP series User Manual
Page 3: Output: 48v, General specifications, Feature specifications, Feature specifications (continued)

GE
Data Sheet
CAR1248FP series rectifier
Input: 90V
AC
to 264V
AC
; Output: 48V
DC
@ 1200W; 5 V
DC
@ 0.5A
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 3
48V
DC
MAIN OUTPUT (continued)
Parameter
Symbol
Min
Typ
Max
Unit
Turn-ON delay
T
2 sec
Remote ON/OFF delay time
40 ms
Turn-ON rise time (10 – 90% of V
OUT
)
50 ms
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/µs, recovery 300µs)
V
OUT
-5 +5 %V
OUT
Programmable range (hardware & software)
42.8
56
V
DC
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
I
OUT
58 59 60 V
DC
Output current V
in
– high line
V
in
– low line
0
25
20.8
A
DC
Current limit, Hiccup (programmable level)
110
130
% of FL
Active current share
-10
+10
% of FL
STANDBY OUTPUT
Parameter
Symbol
Min
Typ
Max
Unit
Set point
V
OUT
5.0 V
DC
Overall regulation (load, temperature, aging)
V
OUT
-5 +5
%
Ripple and noise
50
mVp-p
Output current
I
OUT
0 0.5 A
DC
Overload protection -
1.5
A
DC
Isolation Output/Frame
500
V
DC
General Specifications
Parameter
Min
Typ
Max
Units
Notes
Reliability
100,000
Hrs
Full load, 50C ; MTBF per SR232 Reliability
protection for electronic equipment, method I,
case III,
Service Life
10
Yrs
Full load, excluding fans
Weight
Kgs
(Lbs)
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.
Parameter
Symbol
Min
Typ
Max
Unit
Remote ON/OFF (Needs to be pulled HI via an external resistor)
Logic High (Module ON)
I
IH
20 µA
V
IH
0.7V
DD
12 V
DC
Logic Low (Module OFF)
I
IL
1 mA
V
IL
0
0.8 V
DC
Feature Specifications (continued)