Ge energy, Car2024fp series rectifier – GE Industrial Solutions CAR2024FP series User Manual
Page 6

GE Energy
CAR2024FP series rectifier
Input: 90Vac to 264Vac; Output: 24 Vdc @ 83A; 3.3Vdc or 5 Vdc @ 1A
March 28, 2013
©2012 General Electric Company. All rights reserved.
Page 6
LEDs
Three LEDs are located on the front faceplate. The AC
LED provides visual indication of the INPUT signal
function. When the LED is ON GREEN the power supply
input is within normal design limits.
The second LED DC provides visual indication when the
output is ON. When the LED is GREEN then the DC
output is present.
The third LED FLT provides visual indication when a fault
is present. When the LED is RED then a fault condition
exists and the power supply does not provide output
power.
Alarm Table
Test Condition
LED Indicator
Monitoring Signals
AC OK
DC OK
FAULT
FAULT
DC OK
INPUT OK
TEMP OK
1 Normal
Operation
Green
Green
OFF High High High High
2
Low or NO INPUT
OFF
OFF
Red
Low Low Low High
3 OVP
Green
OFF
Red
Low Low High High
4 Over
Current
Green
OFF
Red
Low Low High High
5
Over Temp Alarm
Green
Green
OFF High High High
Low
6
Over Temp Fault
Green
OFF
Red
Low Low High Low
7
Remote ON/OFF, OFF
Green
OFF
Red
Low Low High High
Note: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.
Outline Drawing