Ge energy, Car2024fp series rectifier – GE Industrial Solutions CAR2024FP series User Manual
Page 3

GE Energy
CAR2024FP series rectifier
Input: 90Vac to 264Vac; Output: 24Vdc @ 83A; 3.3Vdc or 5 Vdc @ 1A
March 28, 2013
©2012 General Electric Company. All rights reserved.
Page 3
24V
dc
MAIN OUTPUT (continued)
Parameter
Device
Symbol
Min
Typ
Max
Unit
Remote ON/OFF delay time
All
40
ms
Turn-ON rise time (10 – 90% of V
out
)
All
60
ms
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/
out
µs, recovery 300µs)
All
V
out
-5 +5
%V
out
Programmable range (hardware & software)
All
21
29
V
dc
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
All
30 31 32 V
dc
Output current V
in
= HL
V
in
= LL
All
I
out
0
83
50
A
dc
Current limit, Hiccup (programmable level)
All
110
130
% of FL
Active current share
All
-5
+5
% of FL
AUXILIARY OUTPUT
Parameter
Device
Symbol
Min
Typ
Max
Unit
Set point
All
V
out
3.3
/
5.0
V
dc
Overall regulation (load, temperature, aging)
All
V
out
-5 +5 %
Ripple and noise
All
50
mVp-p
Output current
All
I
out
0 1
A
dc
Overload protection -
Overvoltage protection
Isolation Output/Frame
All
100
V
dc
Environmental, Reliability
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
Operating
Altitude Operating
Power Derating
-10
4
50
2250/7.4k
2.5
2.0
°C
m / ft
%/°C
C/1000 ft
Air inlet from sea level to 5,000 feet.
51°C to 70C
Above 5,000 ft
Storage
Altitude non-operating
-40
85
8200/30k
°C
m / ft
Acoustic noise
55
dbA
Full load
Over-temperature Protection
125/110
°C
Shutdown / restart
Humidity Operating
Storage
30
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration
6
Grms
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Earthquake Rating
4
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed
and tested to meet NEBS specifications.
Reliability
400,000
Hrs
Full load, 25C ; MTBF per SR232 Reliability protection
for electronic equipment, method I, case III,
Service Life
10
Yrs
Full load, excluding fans
4
Designed to start at an ambient down to -40°C; meet spec after 30 min warm up period, may not meet operational limits below -10°C.