Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection: Circuits are scanned for loads upon module power up and upon manual scan.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/OFF state of each circuit.
The only automatic change in circuit ON/OFF status occurs upon module power up.
Information: Circuit ON/OFF and Load Detection
Manually Scan Circuit Loads: Press and release the Button - no interruption of power to ON circuits.
Manual Circuit ON/OFF:
1. Press and hold the Button to enter the manual mode
hold until the OK LED turns OFF and back ON (2 seconds)
2. Tap the Button repeatedly until the desired Circuit LED blinks
3. Press and hold the Button to toggle the circuit ON/OFF
hold until the OK LED turns OFF and back ON (2 seconds)
4. Repeat from step 2 to operate another circuit
5. Automatic operation is restored after a few seconds of Button inactivity
The OK LED is turned OFF when the button is pressed. It returns to ON when the button is released or after the
button is held for 2 seconds.
Information: Manual Module Operations
Button
Circuit LEDs
Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection: Circuits are scanned for loads upon module power up and upon manual scan.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/OFF state of each circuit.
The only automatic change in circuit ON/OFF status occurs upon module power up.
Information: Fault Detection
Specifications and Application
Specifications and ordering information are in the Power Express Class 2 Distribution Brochure available at
www.gecriticalpower.com
External Surge Protective Device (SPD) is required on all AC inputs.
Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane
(Mesh Bonding Network or Common Bonding Network).
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at
www.gecriticalpower.com
.
Document Title
Power Express Class 2 Distribution Brochure (aka Power Express Class 2 Distribution Ordering Guide )
Circuit LED Blink Pattern
ON
ON with brief blink OFF
OFF
OFF with brief blink ON
Power Express - Quick Start Guide