GE Industrial Solutions Power Express Class 2 User Manual
Page 3
Step 6 - Install Modules
Open latch.
Insert module into Shelf.
Close latch.
Step 7 - Initial Start Up
Verify that all connections are complete and secure.
Turn on the DC input breaker.
Modules automatically start up and scan outputs for loads.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Information: LEDs and Alarm
Shelf LEDs and Alarm
Condition
Shelf LED
OK ALM
Class 2 Circuit ON
G
OFF
-
Class 2 Circuit OFF
G
OFF
-
Class 2 Over Current/Shorted
OFF
Y
Alarm
Class 2 Failed Circuit
OFF
R
Alarm
Input Voltage Very Low
OFF
OFF
Alarm
Input Voltage Out of Range OFF
Y
BLINK
Alarm
Reversed Input Polarity
OFF
R BLINK
Y BLINK
Alarm
Supervisor Circuit(s) Fail
OFF
R
Alarm
I
2
C Comm Fault
OFF
G
-
GP Comm Fault
OFF
R BLINK
Alarm
Shelf Alarm
Condition
Module OK LED
Module Circuit LEDs
2
1 - 8
Priority
1
LED
Circuit - ON
G
G
Circuit - OFF
G
OFF
Circuit - ON - Over Current
3
Y
Y
Circuit - Fail
1
R
R
I
2
C Comm Fault
4
R BLINK
Per Circuit Condition
Interrupter Fail
1
R
OFF
Input Voltage Out of Range
2
Y BLINK
OFF
Input Voltage Very Low or
Reversed Polarity
OFF
OFF
Module LEDs
1. OK LED indicates the highest LED priority. Priority 1 is highest.
2. Each Circuit LED indicates the Condition of its Circuit, independently of the other Circuits.
Latch
3
Power Express - Quick Start Guide
Document 850031168 r05 2013 December