OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual

Page 75

background image

74

QUICKTRONIC

®

30mm height

Max. number of ECGs

with automatic circuit

breakers

Ip[A]

T

H

[µs] 10A

16A

QT-FH 1x14-35 CW

20 210 17

28

QT-FH 2x14-35 CW

20 210 17

28

QT-FQ 1x24 CW

17 155 25

41

QT-FQ 1x39 CW

17 155 25

41

QT-FQ 1x49 CW

20 210 17

28

QT-FQ 1x54 CW

20 210 17

28

QT-FQ 1x80 CW

28 230 8

13

QT-FQ 2x24 CW

20 210 17

28

QT-FQ 2x39 CW

28 230 8

13

QT-FQ 2x49 CW

28 230 8

13

QT-FQ 2x54 CW

28 230 8

13

QT-FH 1x14

17 155 25

41

QT-FH 1x21

17 155 25

41

QT-FH 3x14 CW

20 230 17

28

QT-FH 4x14 CW

20 230 17

28

QUICKTRONIC

®

for FC

Max. number of ECGs

with automatic circuit

breakers

Ip[A]

T

H

[µs] 10A

16A

QT-FC 1x55/230-240 S

28 230 8

13

7.4 Lamp/ECG

Combinations

Valid Lamp-ECG combinations are available in the Lighting Programme.

Edition January 2005 also available in

Section 9 or under

www.osram.com/ecg

7.5 OSRAM

Installation

Tips for T5-Systems

Maximum lamp temperatures for T5/

∅ 16 mm fluorescent lamps compared

to T8/

∅ 26 mm-fluorescent lamps






Max. temp. at lamp caps

Lamp centre

Electrode area

°C

°C

°C

T8/L36W

120

45...55

100...120

T8/L58W

140

50...65

110...130

T5/FH28W

120

40...60

160 (200...250*)

T5/FQ54W

120

50...70

160 (200...250*)

*)

in

FH

-

E

C

G

-

Luminaires

the lamp could be incorrectly used,

e

.

g

. FH35W

with

FQ80W