beautypg.com

OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual

Page 68

background image

67

6.5.1 Different criteria for

lighting

Safety lighting
for escape
route

Antipanic
Lighting

Safety Lighting
for workplaces
with special
danger

Illuminance E

min

1 lx

> 0,5 lx
horizontal on the
ground

10 % of the
maintenance
value of
illuminance
absolutely: 15 lx

Switch-on delay 50 % of the

required
illuminance
within 5 s
100 % within
60 s

50 % of the
required
illuminance
within 5 s
100 %

within

60 s

0,5 s
immediately
specified value
(10 %) has to be
achieved


DIN VDE 0108 includes further information in addition to EN 1838.

In addition to the switch-over times of Electronic Control Gear to operate
T5/

∅ 16 mm fluorescent lamps , mentioned within the next sections, the

switch-over time of the relays have to be considered.
These data are available in the technical relay data.

6.5.1.1 Switch-over time for

QTi – h=21 mm

Lampstart

Preheat

Ignition time for
a) Cold lamp

(Stand-by

mode)

b) warm lamp (i.e.short term

interruption of voltage)


< 1 sec.

< 0.5 sec.


6.5.1.2 Switch-over time for

QT-FH…CW –
h=30 mm

Lampstart

Preheat

Ignition time for
a) Cold lamp

(Stand-by

mode)

b) warm lamp (i.e.short term

interruption of voltage)


< 2 sec.

< 0.5 sec.


6.5.1.3 Switch-over time for

QT-FQ…CW –
h=30 mm

Lampstart

Preheat

Ignition time for
a) Cold lamp

(Stand-by

mode)

b) warm lamp (i.e.short term

interruption of voltage)


< 0.5 sec.

< 0.5 sec.


6.5.1.4 Switch-over time for

QT-…F/CW –
h=21 mm

Lampstart

Preheat

Ignition time for
a) Cold lamp

(Stand-by

mode)

b) warm lamp (i.e.short term

interruption of voltage)


< 0.5 sec.

< 0.5 sec.