OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual
Page 68
67
6.5.1 Different criteria for
lighting
Safety lighting
for escape
route
Antipanic
Lighting
Safety Lighting
for workplaces
with special
danger
Illuminance E
min
1 lx
> 0,5 lx
horizontal on the
ground
10 % of the
maintenance
value of
illuminance
absolutely: 15 lx
Switch-on delay 50 % of the
required
illuminance
within 5 s
100 % within
60 s
50 % of the
required
illuminance
within 5 s
100 %
within
60 s
0,5 s
immediately
specified value
(10 %) has to be
achieved
DIN VDE 0108 includes further information in addition to EN 1838.
In addition to the switch-over times of Electronic Control Gear to operate
T5/
∅ 16 mm fluorescent lamps , mentioned within the next sections, the
switch-over time of the relays have to be considered.
These data are available in the technical relay data.
6.5.1.1 Switch-over time for
QTi – h=21 mm
Lampstart
Preheat
Ignition time for
a) Cold lamp
(Stand-by
mode)
b) warm lamp (i.e.short term
interruption of voltage)
< 1 sec.
< 0.5 sec.
6.5.1.2 Switch-over time for
QT-FH…CW –
h=30 mm
Lampstart
Preheat
Ignition time for
a) Cold lamp
(Stand-by
mode)
b) warm lamp (i.e.short term
interruption of voltage)
< 2 sec.
< 0.5 sec.
6.5.1.3 Switch-over time for
QT-FQ…CW –
h=30 mm
Lampstart
Preheat
Ignition time for
a) Cold lamp
(Stand-by
mode)
b) warm lamp (i.e.short term
interruption of voltage)
< 0.5 sec.
< 0.5 sec.
6.5.1.4 Switch-over time for
QT-…F/CW –
h=21 mm
Lampstart
Preheat
Ignition time for
a) Cold lamp
(Stand-by
mode)
b) warm lamp (i.e.short term
interruption of voltage)
< 0.5 sec.
< 0.5 sec.