Powersolve 600S Seires User Manual
Switched mode dc power sup ply
Unit 8A
Arnhem Road
Newbury. RG14 5RU
Tel: +44 (0) 1635 521858
Fax: +44 (0) 1635 523771
www.powersolve.co.uk
600 S
- Se ries
600 W
SWITCHED MODE DC POWER SUP PLY
Fea tures :
• Very high re li abil ity, MTBF 1.000.000 hrs
• No RFI prob lems, RFI fil ters in out put and in put
• Natural convection cooling
• Meets EN 61000-3-2 and V DE 0160 class 2
• Thermally over-rated for high ambient temperature without derating
• Low inrush current
• Build-in diode for redundant parallel operating
• High efficiency 89%
• Under-voltage alarm contact
• Short circuit protected
• Low output ripple, 7 mV rms
• Analog programmable
Spec i fi ca tions :
• I
nput voltage
: AC 198-264 V 48-62 Hz 3.8 Arms
• Line distortion
: Harmonic current meets EN 61000-3-2
fuse 6.3 A T, crest factor 2.0
• Safety
: EN 60950, EN 61010 SELV / PELV
: AC 99-132 V 48-62 Hz 7.6 Arms
• Output voltage
: Screwdriver adjustable with 10-turn
fuse 12.5 A T
potmeter at the rear side.
: DC contact factory
Factory set at 24.0 V
• Insulation
Also analog programable by 2-5 V
• Input / output
: 3750 V rms (1min)
• Efficiency
: 89% at 230 V AC input and 600 W output
• Input / case
: 2500 V rms (1min)
(max. heat dissipation 74 W)
• Output / case
: 500 V DC
• Temp. coeff
: 5.10-5 per °C
• Stability
: 3.10-4 during, 8 hrs under constant
conditions, after 1 hr warmup.
• Inrush current
: Limited by 47 Ohm (shorted after startup)
• Regulation
Load 0 - 100%
: Better than 10 mV
• Power factor
: 0.76 at 230 V AC input and full load.
line 198-264 V
: Better than 5 mV
• Ripple + noise
: Max 7 mV rms, 20 mV pp (BW = 20 MHz)
• EMC
: EN 61204-3 Power Supply Standard
• Output imp.
: Less than 0.05 Ohm up to 100 kHz
: EN 61000-6-3 Emission (EN 55022B)
• Recovery time
: 0.3 milliseconds to recover to within
: EN 61000-6-2 Immunity
100 mV after a 50 to 100% load step
Max. deviation 300 mV
• VDE0160 impulse test
: Input with stands non periodic impulse
• Hold-up time
: 30 ms at 155 or 230 V AC input and full
2.3 Ûn 1.3 ms of VDE0160 class 2
load. 60 ms at half load.
• Series operations : up to 500 V total voltage
• Parallel oper.
: No restrictions
• Redundant parallel : Use R+ connection via build-in Schottky
operation
diode to separate the outputs. Do not use
remote sensing.
600 S 24
12 -15 V
30 A
24 V
25 A
30 V
20 A
Mod els
Volt age range
Cur rent range
600 S 24
12 -15 V
30 A
24 V
25 A
30 V
20 A