Powersolve HSE01201 Series User Manual
Page 2

Powersolve Electronics Ltd., Unit 8A Arnhem Road, Newbury RG14 5RU, United Kingdom
Tel 0044 (0)1635 521858 Fax 0044 (0)1635 523771
www.powersolve.co.uk
p.2/2 03.12B
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
AC Input
85..132Vac / 184..265Vac , 47…63Hz , 110…375Vdc
AC Input Rating
115Vac <2.2A 230Vac <1.1A
Rated DC Voltage
12V
15V
24V
36V
48V
60V
72V
110V
Rated DC Current
10.0A
8.0A
5.0A
3.3A
2.5A
2.0A
1,7A
1,1A
DC Range (adj.)
11,4..13,2V 14,2..16.5V 22,5..28,5V 34,2..39,6V 45,6..52,8V 57..66V
68..86V
100..120V
Ripple
230Vac 20MHz
50mVpp
50mVpp
65mVpp
65mVpp
100mVpp
120mVpp
120mVpp
380mVpp
Order code: HSE01201.Vout+(T= DIN Rail ; W= wall mount) Example: 24V for DIN-Rail = HSE01201.24T
Tolerance
± 1%
Load regulation
< ± 0.5% 10-100%, 100-10%
Switching Frequency
100KHz typical
Minimum Load
0 A
Efficiency
91% typ.
Load Protection
1,2x I
rated
,auto recovery
Voltage Protection
145% of U
out
, auto recovery
Short Circuit Protection
Continuous
Temperature Control
Upon request
Hold Up Time
> 30ms 230Vac
Inrush Current
< 16A (230Vac)
Terminal Connects:
1 = L
SK1
2 = N
3 = GND
1 = DC +
2 = DC +
SK2
3 = DC -
4 = DC -
5 = relay
(not 72V &
6 = relay
110V)
Screw terminal order codes:
(each package = 10 pcs )
for SK1 1pc (3520038)
SK2 2-3pcs (3520037)
Art.No.: 3520038 (3 pins)
Art.No.: 3520037 (2 pins)
Softstart
50ms typical
Convection
Free air
Ambient Temperature
- 20°C…+70°C
Storage Temperature
- 40°C…+85°C
EMI
EN55022 class B / EN61000-3-2
EMS
EN61000-6-2,3
Safety
cUL60950/1950 , EN60950-1
Safety class 1(A)
VDE0805, VDE0100
Air & Surface Leakage Paths
> 8mm
Input/Output
Galvanic insulated
DC Fail Relay (galv. Insulated)
<48Vdc/500mA (not 72V, 110V)
MTBF rated
400000h
Dimensions (HxWxD)
124x50x96mm
Weight
510g
Connectors (AC & DC)
Terminal plug AWG26...AWG12
Options for military use available upon request
*normally closed contact
Conception:
The HSE power supply series realizes very high power efficiency in a
space-saving housing. This design enables Green Power applications
and allows free air convection. Latest generation electrical devices
relate to the high reliability of all Camtec products. The Camtec
philosophy is, to employ 125°C low ESR ultra long life capacitors
where expedient to achieve a superior lifetime of our products. The
used screw terminal plugs allow easy to wire, smooth service and
protect you from mix-up the input with the output signals.
Parallel Operation Mode:
Parallel operation of equal HSE-Power-Supplies provides you
a higher output power. Make sure that the DC voltages differ
at only ±1% and that DC cables are of equal length.
Series Operation Mode:
To raise the output voltage you can drive equal HSE power
supplies in series, too.