beautypg.com

Powersolve 2UPSWI Series User Manual

Dc-ac inverters, Features

background image

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England

Tel: 01635 521858 Fax: 01635 523771 Email: [email protected]

www.powersolve.co.uk

DC-AC INVERTERS

2UPSWI Series
Pure Sine Wave
2000 & 3000 Watts

Features:

12V, 24V, 48V, 110V or 220V DC Inputs

• High Surge Rating
• 50/60 Hz Pure Sine Wave Output
• 100-120 or 200-240VAC Output Voltage
• 2U 19” Rack Mounting

Electrical Specification

DC Inputs:

12V, 24V, 48V, 110V, 220V DC (see table below)

Output Voltage:

100 to 120VAC (tune VR) or 200-240VAC (tune VR)

Output Frequency:

50/60Hz switch selectable

Output Power:

2000W or 3000W continuous depending on model

Surge Rating:

2000W model, 2300W 3 mins, 2500W 3 secs & 4000W peak
3000W model, 3200W 3 mins, 3500W 3 secs & 6000W peak

Peak Output Current (120/240VAC):

25A/11A 2000W & 30A/15A 3000W

No Load Input Current:

See table

Output Waveform:

R Load pure sinewave <3% THD

Power Factor:

1.0

Protection:

Overload, short circuit, reverse polarity (fuse),
over/under input voltage, over temperature

Digital Display:

OVP, UVP, OTP, OLP, VAC, Amps, Watts, VDC, Temp, Hz

Interface Control Port:

RS232 baud rate 2400, 4800, 9600, 19200 switch select

Remote Control Unit:

Optional - consult sales office for details

AC Input (for UPS use):

Either nominal 110VAC or 220VAC, depending on model

AC Input Frequency:

50~60Hz ±3%

Bypass Switchover Time:

4~6mS

Operating Temperature Range:

-20ºC to +50ºC

Storage Temperature Range:

-30ºC to +70ºC

Cooling:

Thermostatically controlled integral fan

Dimensions (in mm):

424W X 435D X 88H

Output Socket:

Optional, UK, Euro, USA , Australia & NZ or Universal

Weight:

2000W 12.8kgs, 3000W 14.3kgs

Safety:

EN60950-1, UL458 on 1500W 120VAC output model

EMC:

2000W Models

FCC ‘A’ (110V output), EN55022’A’, EN55024, EN61000-3-2,
EN61000-3-3, EN61000-4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11

3000W Model

FCC’A’ (110V input), EN55022’A’, EN61000-3-2, EN61000-3-3