beautypg.com

Powersolve Ethernet Interface User Manual

Page 2

background image

PSC-ETH

Analog inputs and outputs

The 2 analog in- and outputs have a 16 bits resolution. Offset and full scale can be software calibrated.
Input linearity error is +/- 1 LSB, output linearity error is +/- 2 LSB. TC typical is 10 ppm / °C.
Each analog in- and output can be set or read. Analog voltages are standardized on 0 - 5 V.
An a log in- and out puts have a com mon zero.

Status monitoring

The PSC provides logic status inputs to monitor the status signals of the power supply such as
CC mode, current or voltage limit, DC fail, AC fail, Over Temperature, PSOL, etc.

Controls

Remote ShutDown: Enables / disables the output voltage of the power supply.
REMOTE: Switches from manual control to remote control (not on PSC-ETH module)

Digital User Inputs and Outputs

The PSC-ETH provides eight 1000 V opto-isolated logic inputs with common zero for custom use.
The input impedance is 1800 Ohm, Logic high = 2.5 ... 30 V, Logic low = 0 V.
The PSC-ETH provides also six 1000 V opto-isolated, logic, open drain outputs with common
zero for custom use. The output impedance is 7 Ohm, maximum rating is 30 V / 200 mA.

Accessoiries

PSC ETH built-in:

CD-ROM with example software and manual in PDF format.

PSC ETH module:

CD-ROM with example software and manual in PDF format, Analog cable and Line Cord.

Spec i fi ca tions ex ter nal mod ule PSC-ETH mod ule

Dimensions (h x w x d)

89 x 85.5 x 118.5 mm, 0.7 kg

Input Power

Wide range 98-264 V AC, 48-62 Hz
Power consumption 10 W
Hold-up time @ 110 V AC : 80 ms

Hold-up time @ 230 V AC : 300 ms

Ambient temperature

Operating 0 to +55 °C
Storage −20 to +70 °C

Isolation

Analog in- and outputs to case:

1000 V DC

Logic in- and outputs to case:

1000 V DC

Ethernet to case:

1000 V DC

Line input to case:

2500 V AC

EMC

Emission : EN 61000-6-3, residential, light industrial environment

EN 55022B

Immunity : EN 61000-6-2, industrial environment
Enclosure: IP20

The Sequencer

The PSC-ETH can control the power supply by a sequence without the need of an external computer.
The sequencer can even control the user outputs and read the user inputs.
A sequence is built from user programmable steps (or program lines).
A sequence step can do the following:

• Set the output Voltage and Current

• Possibility to create loops, subroutines, ramps ect.

• Jump to defined step number, unconditional or under condition of:

• Set a Digital output (6 available )

• Digital outputs, Digital inputs, Variable, output voltage or current

• Wait for trigger from Computer or Pause

• Increment or Decrement output Voltage, Current or Variable

• Set a internal Variable (8 available) or an internal Timer (2 available)

Sequences can be started / paused / stopped by : Commands via Ethernet (software) or by User Inputs (hardware).

Using digital user inputs for starting or stopping a sequence, makes it possible to choose the sequences by
selecting the corresponding input, without being connected to a computer.

ES 150

Op tion P150 ES150 Se ries with Build-in Card Not avail able

An a log pro gram ming con nec tor re moved

ES 300

Op tion P179 ES300 Se ries with Build-in Card Not avail able

An a log pro gram ming con nec tor re moved

SM 800

Op tion P256 ES800 Se ries with Build-in Card Avail able

An a log pro gram ming con nec tor still avail able

SM 1500

Op tion P177 ES1500 Se ries with Build-in Card Avail able

An a log pro gram ming con nec tor still avail able

SM 3000

Op tion P149 ES3000 Se ries with Build-in Card Not avail able

An a log pro gram ming con nec tor re moved

SM 6000

Op tion P157 ES6000 Se ries with Build-in Card Avail able

An a log pro gram ming con nec tor still avail able**

Mod els

Or der Code De scrip tion

Dig i tal User I/O

Com ments

**Note : Ex cept on SM 600-10 and SM 300-20