PowerWalker SNMP DP-522 User Manual
Page 91
2. Use FTP to update (suitable for BK,CK,DK,BP,CP,DP using firmware version
2.35 and later)
The FTP is a easy and common way to upload the latest firmware into the NetAgent.
Please follow the instruction below to update the firmware. If there is other FTP client
application on your computer, that will also be fine to use it for updating the firmware.
For example: if wish to update the latest firmware of the NetAgent UPS which IP address
is 192.168.50.179, then please operate with the steps below:
(1) Enter Windows, then type ftp 192.168.50.179 under “Run” of the “Start Menu”
(2) After executed, the systems will requests for the user name and password. Please enter
“admin” under the user name and enter the password that was been set at Netility under
password. If did not set before, then please enter the default value as user name: “admin”
and nothing under password. (press “Enter”).
- Once the account and password been checked, the server will response with 230 OK to
indicate Login succeeded.
- If entered wrong account and password, the server will response with 530 Not Logged in to
indicate Login failed.
(3) Operation commands as followings:
-1s: This command is to request server to list up all the file and sub file under current Menu.
User may finds out the firmware version of the NetAgent UPS of its IP.
-put
Server point. User may use this method to upload the latest firmware to the remote
NetAgent
-quit: This command is to allow the user to logout with the current username account as well
as close the connection of FTP.
For example: The picture below is to upload the latest NetAgent firmware file (c:\
work\netagent\prjs\nag\2.32.DK520.bin ) which is in this computer to the NetAgent UPS with
IP address of 192.168.50.179
85