- 4 -

FireSwitch108

enclosure UL Listed for appropriate application. Separate battery enclosure is required to have 50 cubic inches of

additional open space. All wiring methods shall be in accordance with the National Electrical Code

NFPA 70/NFPA 72/ANSI/Canadian Electrical Code/CAN/ULC-S524/ULC-S527/ULC-S537 and with all local codes

and authorities having jurisdiction. Battery circuits are not power limited provide 0.25” spacing from power limited

circuits use separate knockout. If additional battery enclosure is required it must be UL Listed for the application

and mounted within 5’ of the FireSwitch enclosure in the same room, minimum 12 AWG wire in appropriate

conduit is required for connection. When using conduit, make sure it is installed in a matter where it can not turn.

4. To trigger NAC outputs via the FACP signaling circuit(s) (polarity reversed) set INP1 and INP2 dip switches to

the OFF position. To trigger NAC outputs via the FACP dry relay contact (normally closed NC) set INP1

and INP2 dip switches to the ON position (Fig. 2a, pg. 4).

5. Determine the functionality of outputs [OUT1 through OUT8]. Outputs can be programmed as Class “A” NACs,

Class “B” NACs, Aux. power output(s) with battery backup or Aux. power output(s) without battery backup.

Note: Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have

chosen will work with this feature.

Note: When programming outputs for Aux. power it will not be affected by the FACP trigger input.

(Refer to Fig. 4, pg. 7 for Wiring, for Programming refer to pg. 8).

6. Determine which NAC input will trigger the desired NAC output(s).
7. Select output options (for Programming refer to pgs. 8-12).

Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with

synchronization capability.

Battery 1

Battery 2

Green

Lead

Battery connections are (non-power limited):

Use two (2) 12V battery hook-up in series

Door

Wire

Strap

(from

Enclosure

to Door)

unswitched

120VAC 60 Hz

INP1

RET1

INP2

RET2

OUT1 OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

Non-power

limited

Non-power

limited

Power

Limited

Regulated

Power Limited Outputs - Regulated

2.5 amp per output in alarm (Supervised)

When programmed for AUX - Special Application only

Inputs

Power Limited

+ SYNC

---
GF1

GF2

NC

NO

C

EA

RT

H

NEGA

TIV

E

POSITIV

E

ETHERNET

RIGHT

LEFT

UP

DOWN

PRESS DOWN

FOR ENTER

Power

Limited

+

24V

--

+

AUX

--

BA

T F

AIL

AC
FA

IL

+

BA
T
–+

DC

--

DC

AC

AC DELA

Y

NC

C

NO

NC C

NO

Class 1

AC LOCA

L

NC

C NO

L

N

Battery and AC Supervision

Circuit (power limited).

Use separate knockout.

Keep 1/4" spacing from power limited wiring and non-power limited wiring

5A
250V

INP2
INP1
INP2
INP1

ON

INP2
INP1
INP2
INP1

ON

Dip Switch

Non-Power Limited

Non-

Power

Limited

15

15

A

32

V

Fig. 2

Fig. 2a