Altronix OLS180 Installation Instructions User Manual
Ols180 - offline switching power supply/charger
Overview:
The OLS180 is a power supply/charger that converts 115VAC / 60Hz input, into a 12VDC or 24VDC @ 6 amps
of continuous supply current (see specifications).
Specifications:
• 12VDC or 24VDC selectable output.
• 6 amp continuous supply current.
• Input 115VAC / 60Hz, 1.9 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current .5 amp.
• Automatic switch over to stand-by battery when AC fails (zero voltage drop).
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
• Short circuit and thermal overload protection.
• Power ON/OFF switch.
• Includes battery leads.
Board Dimensions: 4.5”W x 7.25”L x 1.75”H
Specified at 25˚ C ambient.
Voltage Output Selection Table:
Output VDC
Switch Position
Max. Load DC
12VDC
SW 1 - Closed
6 amp
24VDC
SW1 - Open
6 amp
Installation Instructions:
The OLS180 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the OLS180 in desired location/enclosure.
2. Slide [Power ON/OFF] switch to OFF position.
3. Set the OLS180 to desired DC output voltage via SW1 (Voltage Output Selection Table).
4. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
5. Measure output voltage before connecting devices. This helps avoid potential damage.
6. Connect devices to be powered to terminals marked [– DC + ].
7. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect battery to terminals marked [– BAT +] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
8. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory
relay outputs marked [NC, C, NO].
9. Slide [Power ON/OFF] switch to ON position.
OLS180 - Offline Switching
Power Supply/Charger