beautypg.com

Altronix PD4CB Installation Instructions User Manual

Pd4cb - power distribution module, Overview, Specifications: input

background image

PD4CB - Power Distribution Module

Overview:

The PD4CB power distribution module converts a single AC or DC input into four (4) PTC protected outputs.

Specifications:
Input:

• Handles up to 28VAC/VDC.

Outputs:

• Four (4) PTC protected outputs (PTC’s are rated @ 2.5 amp).
• Surge suppression.

Visual Indicators:

• Power output LED indicator.

Additional Features:

• Power ON / OFF switch.

Board Dimensions (approximate):

5.25"L x 3.25"W x 1"H

Installation Instructions:

1. Mount PD4CB in desired location/enclosure.
2. Connect the desired power supply output to terminals marked [INPUT] (Fig. 1A).

Note: If using DC voltage, left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1A).

3. Measure output voltage before connecting devices. This helps avoid potential damage.
4. Set power switch [SW1] to the OFF position.
5. Connect each device to terminal pairs 1 to 4, marked [1P-1N thru 4P - 4N].
6. Set power switch [SW1] to the ON position.

INPUT

1P

1N

2P

2N

LED

1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS

ON

OFF

SW1

F1

3P

3N

4P

4N

F2

F3

F4

NP

S

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIPD4CB - Rev. 112204

K22D

MEMBER

Fig. 1

INPUT

1P

1N

2P

2N

LED

1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS

ON

OFF

SW1

F1

3P

3N

4P

4N

F2

F3

F4

NP

S

Neg. (--- )

Pos. (+ )

Fig. 1A