14 supplement, 1 technical data, 14 .1 technical data – VEGA VEGATOR 632 User Manual
Page 54
14
Supplement
14
.1 Technical data
General data
Series
Module unit with plug-in socket for mounting on
carrier rail 35 x 7.5 or 35 x 5 according to EN 60715
Weight
170 g (6 oz)
Housing material
Housing: Polycarbonate, front cover: Polypropylene
PPN
Fixing slide for rail fastening
Polyamide PA6
Power supply - Alternating voltage version AC
Operating voltage
85 … 253 V AC, 50/60 Hz
Max. power consumption
4.5 W
Power supply - Direct voltage version DC
Operating voltage
20 … 30 V AC, 50/60 Hz, 20 … 60 V DC
Max. power consumption
1.2 W (at 20 V)
Sensor input
Quantity
2 x level detection or 1 x pump control (min./max.)
Response resistor
1 … 200 kΩ adjustable
Measuring circuit
max. 5 V eff., max. 1 mA
Permissible line capacitance
1 x 100 nF or 2 x 70 nF with min./max. control
Switching hysteresis
15 %
Relating to the conductivity of the medium
Adjustment elements
DIL switch block
For preadjustment of the damping and the mode
Potentiometer
for switching point adjustment
Control lamps in the front plate
-
Status indication operating voltage
Signal lamp green (LED)
-
Status indication fault signal
Signal lamp red (LED)
-
Status indication switching point control
2 signal lamps yellow (LED)
Relay output
Number - Relay outputs
-
Level relay (spdt)
1
-
Fail safe relay (spdt)
1 (adjustable as second level relay)
Mode (adjustable)
Max. detection or overfill protection or min. detec-
tion or dry run protection
54
VEGATOR
632 • Signal conditioning instrument
14 Supplement
35243
-EN
-120228