beautypg.com

14 supplement, 1 technical data, 14 .1 technical data – VEGA VEGATOR 632 User Manual

Page 54

background image

14

Supplement

14

.1 Technical data

General data

Series

Module unit with plug-in socket for mounting on
carrier rail 35 x 7.5 or 35 x 5 according to EN 60715

Weight

170 g (6 oz)

Housing material

Housing: Polycarbonate, front cover: Polypropylene
PPN

Fixing slide for rail fastening

Polyamide PA6

Power supply - Alternating voltage version AC

Operating voltage

85 … 253 V AC, 50/60 Hz

Max. power consumption

4.5 W

Power supply - Direct voltage version DC

Operating voltage

20 … 30 V AC, 50/60 Hz, 20 … 60 V DC

Max. power consumption

1.2 W (at 20 V)

Sensor input

Quantity

2 x level detection or 1 x pump control (min./max.)

Response resistor

1 … 200 kΩ adjustable

Measuring circuit

max. 5 V eff., max. 1 mA

Permissible line capacitance

1 x 100 nF or 2 x 70 nF with min./max. control

Switching hysteresis

15 %
Relating to the conductivity of the medium

Adjustment elements

DIL switch block

For preadjustment of the damping and the mode

Potentiometer

for switching point adjustment

Control lamps in the front plate

-

Status indication operating voltage

Signal lamp green (LED)

-

Status indication fault signal

Signal lamp red (LED)

-

Status indication switching point control

2 signal lamps yellow (LED)

Relay output

Number - Relay outputs

-

Level relay (spdt)

1

-

Fail safe relay (spdt)

1 (adjustable as second level relay)

Mode (adjustable)

Max. detection or overfill protection or min. detec-
tion or dry run protection

54

VEGATOR

632 • Signal conditioning instrument

14 Supplement

35243

-EN

-120228