Fig. 6: Additional electronics for line break monitoring in conjunction with a
conductive probe

1

Connect the eyelet according to the following illustration.

Make sure that the eyelets have no contact to other metal parts.

2

Open one of the other terminals and attach the additional
electronics.

3

Tighten the terminal.

1

2

Fig. 7: Mounting of the additional electronics for line break monitoring

1

Connection to terminal 1 (ground rod = longest rod)

2

Connection to terminal 2 (max. rod = shortest rod)

3

Additional electronics for line break monitoring

If you are using a probe without additional electronics for line break
monitoring, a fault signal will be triggered.

Keep in mind that in case of a fault signal also the switching output will
be activated.

Only failures of channel 1 are monitored.

14

VEGATOR

632 • Signal conditioning instrument