4 activate line break monitoring, 5 master/slave function – VEGA VEGATOR 632 User Manual
Page 34
Note:
When carrying out switching point adjustments keep in mind that there
is a switching delay of 0.5 sec between the moment when the
switching point is reached and the moment when the switching
function is triggered. The potentiometer must therefore be turned
slowly.
A possible additional switching delay should only be switched on after
the adjustment.
The following switching delays can be selected with the 3-step switch.
l
6 s
l
3 s
l
0.5 s
8
.4 Activate line break monitoring
The line break monitoring or alarm function defines the function of the
instrument in case of failure.
If you are using a probe without line break monitoring, a fault signal will
be triggered. In this case, set the switch (7) to off.
Only failures of channel 1 are monitored.
A failure is signalled via the red control lamp on the front plate.
Alarm
off on
1
2
3
4
5
6
7
Fig. 99: Switch block (A) with switch (7) for activation of the line break monitoring
(alarm)
You find detailed information on how to trigger a fault signal via the
second relay output in the previous chapter "Adjust relay function".
8
.5 Master/Slave function
Adjust the instrument as Master with switch 8 of the DIL switch block
(A).
Definition of the instru-
ment as Master or Slave
(DIL switch block A)