beautypg.com

4 activate line break monitoring, 5 master/slave function – VEGA VEGATOR 632 User Manual

Page 34

background image

Note:
When carrying out switching point adjustments keep in mind that there
is a switching delay of 0.5 sec between the moment when the
switching point is reached and the moment when the switching
function is triggered. The potentiometer must therefore be turned
slowly.

A possible additional switching delay should only be switched on after
the adjustment.

The following switching delays can be selected with the 3-step switch.

l

6 s

l

3 s

l

0.5 s

8

.4 Activate line break monitoring

The line break monitoring or alarm function defines the function of the
instrument in case of failure.

If you are using a probe without line break monitoring, a fault signal will
be triggered. In this case, set the switch (7) to off.

Only failures of channel 1 are monitored.

A failure is signalled via the red control lamp on the front plate.

Alarm

off on

1

2

3

4

5

6

7

Fig. 99: Switch block (A) with switch (7) for activation of the line break monitoring
(alarm)

You find detailed information on how to trigger a fault signal via the
second relay output in the previous chapter "Adjust relay function".

8

.5 Master/Slave function

Adjust the instrument as Master with switch 8 of the DIL switch block
(A).

Definition of the instru-
ment as Master or Slave
(DIL switch block A)

34

VEGATOR

632 • Signal conditioning instrument

8 Set up - Two-point control Δs (pump control)

35243

-EN

-120228