VEGA VEGATOR 632 User Manual

Page 21

background image

Note:
When carrying out switching point adjustments keep in mind that there
is a switching delay of 0.5 sec between the moment when the
switching point is reached and the moment when the switching
function is triggered. The potentiometer must therefore be turned
slowly.

A possible additional switching delay should only be switched on after
the adjustment.

Control lamps (LED) in the front plate indicate operation, switching
status and fault signal.

TOR

149A

ON

3

4

1

2

Fig. 15: Control lamps in the instrument front (C)

1

Control lamp - Operating voltage - green (gn)

2

Control lamp - Fault signal - red (rd)

3

Control lamp - Switching status channel 2 - yellow (ye)

4

Control lamp - Switching status channel 1 - yellow (ye)

l

Green (gn)

-

Operating control lamp

-

Mains voltage on, instrument is operating

l

Red (rd)

-

Failure lamp

-

Fault on the sensor circuit due to sensor failure or line break

-

If the fail safe relay is deenergized, the red failure lamp will
light

l

Yellow (ye)

-

Relay control lamps

-

The yellow relay control lamps react depending on the set
mode (min./max.)

-

The relay control lamp generally indicates the activated
(energized) condition of the relay

-

A dark relay control lamp means that the relay is deenergised

Signal lamps (C)

VEGATOR

632 • Signal conditioning instrument

21

6 Adjustment elements

35243

-EN