3
Turn potentiometer (B) slowly clockwise until the relay output
switches and the yellow control lamp changes condition
4
Turn the potentiometer approximately 15° in the same direction
If the relay output has switched, empty the vessel until the electrode is
uncovered.
The relay output must now switch again.
Note:
A failure exists, if the relay output does not switch over even in the last
range. You will find instructions for fault rectification in chapter
"M
aintenance and fault rectification".
7
.3 Adjust switching delay
Adjust the switching delay for the instrument with the slide switch (E).
O
N
3
1
3362
6 s
3 s
0,5 s
1
2
3
4
5
6
7
8
Fig. 56: Slide switch (E) for setting the switching delay
The adjusted switching delay refers to the switching function of the
relay and applies only to the switch on delay.
Note:
When carrying out switching point adjustments keep in mind that there
is a switching delay of 0.5 sec between the moment when the
switching point is reached and the moment when the switching
function is triggered. The potentiometer must therefore be turned
slowly.
A possible additional switching delay should only be switched on after
the adjustment.
The following switching delays can be selected with the 3-step switch.
l
6 s
l
3 s
l
0.5 s
7
.4 Activate line break monitoring
The line break monitoring or alarm function defines the function of the
instrument in case of failure.
Adjustment of the swit-
ching delay (slide switch
E)
VEGATOR
632 • Signal conditioning instrument
27
7 Set up - Single channel control (level detection)
35243
-EN