beautypg.com

3 adjust switching delay, 4 activate line break monitoring – VEGA VEGATOR 632 User Manual

Page 27

background image

3

Turn potentiometer (B) slowly clockwise until the relay output
switches and the yellow control lamp changes condition

4

Turn the potentiometer approximately 15° in the same direction

If the relay output has switched, empty the vessel until the electrode is
uncovered.

The relay output must now switch again.

Note:
A failure exists, if the relay output does not switch over even in the last
range. You will find instructions for fault rectification in chapter
"M

aintenance and fault rectification".

7

.3 Adjust switching delay

Adjust the switching delay for the instrument with the slide switch (E).

O

N

3

1

3362

6 s

3 s

0,5 s

1

2

3

4

5

6

7

8

Fig. 56: Slide switch (E) for setting the switching delay

The adjusted switching delay refers to the switching function of the
relay and applies only to the switch on delay.

Note:
When carrying out switching point adjustments keep in mind that there
is a switching delay of 0.5 sec between the moment when the
switching point is reached and the moment when the switching
function is triggered. The potentiometer must therefore be turned
slowly.

A possible additional switching delay should only be switched on after
the adjustment.

The following switching delays can be selected with the 3-step switch.

l

6 s

l

3 s

l

0.5 s

7

.4 Activate line break monitoring

The line break monitoring or alarm function defines the function of the
instrument in case of failure.

Adjustment of the swit-
ching delay (slide switch
E)

VEGATOR

632 • Signal conditioning instrument

27

7 Set up - Single channel control (level detection)

35243

-EN

-120228