Set up - Single channel control (level
detection)
7
.1 Adjust relay function
3-step switch. The individual switch positions are assigned as follows:
1
2
3
4
5
6
7
8
O
N
3
1
3362
CH1 output parallel
CH2 output separate
CH1 with alarm
Fig. 18: Slide switch for adjustment of the relay outputs (D)
l
CH
1 output parallel - Both relay outputs switch in parallel
l
CH
2 output separate - Relay outputs switch separately
l
CH
1 with alarm - Fault signal with relay output 2
The following charts provide an overview of the relay switching
conditions and the control lamps depending on the adjusted mode and
level.
Level detection with one switching point
l
Min. (dry run protection) or mac. (overfill protection)
l
Channel 1 (relay 1) and channel 2 (relay 2) switch in parallel (CH 1
output parallel)
Mode
Level
Channel 1
Channel 2
Control lamps
max.
6
4
5
16
17
15
ye ye
gn rd
max.
6
4
5
16
17
15
ye ye
gn rd
min.
6
4
5
16
17
15
ye ye
gn rd
Adjustment of the relay
outputs (slide switch D)
CH 1 output parallel
VEGATOR
632 • Signal conditioning instrument
23
7 Set up - Single channel control (level detection)
35243
-EN