beautypg.com

VEGA VEGATOR 632 User Manual

Page 26

background image

1

Set DIL switch 1 to 3 on the DIL switch block (A) according to the
following illustration

1 K

Ω

10 K

Ω

200 K

Ω

10 K

Ω

CH1

CH2

max.

max.

off on

1

2

3

4

5

6

7

Fig. 54: Medium: Liquids in the resistance range up to 10 kΩ

2

Turn potentiometer (B) to complete left position

3

Turn potentiometer (B) slowly clockwise until the relay output
switches and the yellow control lamp changes condition

4

Turn the potentiometer approximately 15° in the same direction

5

If the relay output does not change, you have to switch to the next
range (1 kΩ).

If the relay output has switched, empty the vessel until the electrode is
uncovered.

The relay output must now switch again.

Adjustment in liquids with resistance range up to 1 kΩ

Specifications:

The probe is covered with medium.

1

Set DIL switch 1 to 3 on the DIL switch block (A) according to the
following illustration

1 K

Ω

10 K

Ω

200 K

Ω

1 K

Ω

CH1

CH2

max.

max.

off on

1

2

3

4

5

6

7

Fig. 55: Medium: Liquids in the resistance range up to 1 kΩ

2

Turn potentiometer (B) to complete left position

Medium: Liquids in the
resistance range up to
1

26

VEGATOR

632 • Signal conditioning instrument

7 Set up - Single channel control (level detection)

35243

-EN

-120228