Relay outputs, Settings in the "extended menu – VEGA VEGAMET 514 User Manual
Page 40
40
VEGAMET 514
Settings in the "extended menu"
Relay outputs
In the menu item "
prop. to
" you choose a
parameter that the relay will react to. You can
choose between percent and volume ("prop.
to volume" is useful when under "Conditioning
- Linearisation curves", for example, a spheri-
cal tank or a user programmable lin. curve is
chosen). In the next menu item you can
choose the suitable
Unit
. In the menu item
"
Mode
", the mode of the relay can be chosen.
The individual relay modes are described on
the following pages.
If mode "Tendency rising" or "Tendency
falling" is selected, the menu items "Devia-
tion", "Dev. per time", "Cycle time" and
"Number of cycles" appear.
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Adjust-
ment
Signal
condi-
tioning
Out-
puts
Cur-
rent
out-
puts
Volt
outputs
Relay
outputs
Relay
output
1
Relay
output
2
prop.
to
Per-
cent
Unit
0,0%
Mode
Over-
fill
protec.
Low
%
0,0
Failure
mode
off
Add'l
func-
tions
Scan
time
s
1
Number
of
scan
10
like relay output 1
High
%
100,0
Devia-
tion
s
1,0
De-
viation
per
time
Switch-
ing
delay
t off
s
0
Volume
Height
Pressure
Dry run protec.
Switching window on
Switching window off
Tendency rising
Tendency falling
(monitoring)
0,00 %
Tare %
hold
t on
s
0
With all other modes, the menu items "Low"
and "High" appear. There you can determine
the switching points for the relay.
The menu item "
Failure mode
" always ap-
pears. "Failure mode off" causes the relay to
deenergise when a failure (e.g. sensor
shortcircuit) occurs. "Failure mode hold"
causes the actual relay status to be
maintained when a failure occurs.
Under "Add’l functions", you can adjust a
switch on delay (t on) and a switch off delay
(t off) of the relay to a max. of 600 s (with the
relay modes "Tendency rising" or "Tendency
falling" no switching delay can be set).
Moni-
toring
Low &
High