beautypg.com

Relay outputs, Settings in the "extended menu – VEGA VEGAMET 514 User Manual

Page 40

background image

40

VEGAMET 514

Settings in the "extended menu"

Relay outputs

In the menu item "

prop. to

" you choose a

parameter that the relay will react to. You can
choose between percent and volume ("prop.
to volume" is useful when under "Conditioning
- Linearisation curves", for example, a spheri-
cal tank or a user programmable lin. curve is
chosen). In the next menu item you can
choose the suitable

Unit

. In the menu item

"

Mode

", the mode of the relay can be chosen.

The individual relay modes are described on
the following pages.

If mode "Tendency rising" or "Tendency
falling" is selected, the menu items "Devia-
tion", "Dev. per time", "Cycle time" and
"Number of cycles" appear.

Param.
TAG-
No. 1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condi-
tioning

Out-
puts

Cur-
rent
out-
puts

Volt
outputs

Relay
outputs

Relay
output
1

Relay
output
2

prop.
to

Per-
cent

Unit

0,0%

Mode

Over-
fill
protec.

Low

%

0,0

Failure
mode

off

Add'l
func-
tions

Scan

time
s

1

Number
of

scan

10

like relay output 1

High

%

100,0

Devia-
tion
s

1,0

De-
viation
per
time

Switch-
ing
delay

t off

s

0

Volume
Height
Pressure

Dry run protec.
Switching window on
Switching window off
Tendency rising
Tendency falling
(monitoring)

0,00 %
Tare %

hold

t on

s

0

With all other modes, the menu items "Low"
and "High" appear. There you can determine
the switching points for the relay.
The menu item "

Failure mode

" always ap-

pears. "Failure mode off" causes the relay to
deenergise when a failure (e.g. sensor
shortcircuit) occurs. "Failure mode hold"
causes the actual relay status to be
maintained when a failure occurs.

Under "Add’l functions", you can adjust a
switch on delay (t on) and a switch off delay
(t off) of the relay to a max. of 600 s (with the
relay modes "Tendency rising" or "Tendency
falling" no switching delay can be set).

Moni-
toring

Low &
High