6 adjustment – VEGA VEGAMET 514 User Manual
Page 37
VEGAMET 514
37
Signal
condi-
tioning
Scaling
Lin.
curve
linear
Integr
ation
time s
0
Density
in
Kg/dm
3
1,000
DK
value
(Er)
81,00
Settings in the "extended menu"
7.6 Adjustment
Param.
TAG-
No. 1
Adjust-
ment
with
medium
without
medium
Min-
adjust
at %
0,0
Max-
adjust
at %
100,0
Adjust-
ment
mA
Offset
cor-
rection
0%
at
mA
4,000
100%
at
mA
20,000
Sensor
unpres-
sur'd?
OK ?
Offset
corr.
Now!
OK ?
TAG -
No. 1
%
xx,x
The
adjustment with medium
corresponds
to the procedure in the reduced menu (see
appropriate chapter).
- if the medium is changed later on (medium
with another density value or DK value)
and no new adjustment can be made
or
- if the MET indication and the DIS outputs
relate to height in meters,
please note the following:
In applications with hydrostatic pressure
transmitters, the adjusted density value must
correspond to the value of the medium. In
applications with capacitive electrodes, the
adjusted DK value must correspond to the
value of the medium (water has a density of
1.0 kg/dm
3
and a DK value of 81.00).
For the
adjustment without medium,
two
anticipated values for level, gauge, etc.
corresponding to 0% and 100% must be
entered.
The menu item "Offset correction" is opened
when hydrostatic pressure transmitters are
connected. The offset correction should be
carried out after installation of the sensor as
the sensor values can differ slightly due to
different installation positions (vertical or
horizontal installations). With the offset cor-
rection, the meas. data of the unpressurised
sensor (vessel empty) are detected as cor-
rection values and taken into account in all
subsequent measurements.