CRLSxx
INSTALLATION GUIDE
CALIBRATION PROCESS
1. Connect hose to plastic port located on sensing module.
2. Start flowing nitrogen gas (0 ppm CO2 only).
3. Enter Calibration mode as described on page 3.
NITROGEN
GAS
Regulator
Valve
STEP 1
Calibration Port
STEP 2
Flow Nitrogen.
STEP 3
Calibrate for 5 min. Unit will return to
working display when finished.
Connect hose here
ABC CALIBRATION ALGORITHM
ABC (Automatic Baseline Calibration) is a patented self-calibration feature that
automatically adjusts the CO2 sensor to compensate for drift. When ABC is enabled,
the lowest reading within every 24-hour period is recorded and analyzed over
a running 7 day or 28-day period. If a statistically significant amount of drift is
detected, an automatic correction factor is applied. This enables the sensor to operate
within specifications for the 5-year calibration interval.
NOTE: After changing the ABC settings, the unit will need to be power cycled for the
changes to take effect.
OUTPUT SCALING
Output scaling: 0-2000ppm
CO2 ppm
0-5 Volt
Output
0-10 Volt
Output
mA
Output
Outside
300-500
0.75 to 1.25
1.5 to 2.5
6.4 to 8
Over Ventilated
Under 600 under 1.5
Under 3
Under 8.8
Ideal Ventilation 600-900
1.5 to 2.25
3 to 4.5
8.8 to 11.2
Under Ventilated Over 900
over 2.25
Over 4.5
Over 11.2