CRLSxx

INSTALLATION GUIDE

CALIBRATION PROCESS

1. Connect hose to plastic port located on sensing module.

2. Start flowing nitrogen gas (0 ppm CO2 only).
3. Enter Calibration mode as described on page 3.

NITROGEN

GAS

Regulator

Valve

STEP 1

Calibration Port

STEP 2

Flow Nitrogen.

STEP 3

Calibrate for 5 min. Unit will return to

working display when finished.

Connect hose here

ABC CALIBRATION ALGORITHM

ABC (Automatic Baseline Calibration) is a patented self-calibration feature that
automatically adjusts the CO2 sensor to compensate for drift. When ABC is enabled,

the lowest reading within every 24-hour period is recorded and analyzed over
a running 7 day or 28-day period. If a statistically significant amount of drift is
detected, an automatic correction factor is applied. This enables the sensor to operate
within specifications for the 5-year calibration interval.

NOTE: After changing the ABC settings, the unit will need to be power cycled for the
changes to take effect.

OUTPUT SCALING

Output scaling: 0-2000ppm

CO2 ppm

0-5 Volt

Output

0-10 Volt

Output

mA

Output

Outside

300-500

0.75 to 1.25

1.5 to 2.5

6.4 to 8

Over Ventilated

Under 600 under 1.5

Under 3

Under 8.8

Ideal Ventilation 600-900

1.5 to 2.25

3 to 4.5

8.8 to 11.2

Under Ventilated Over 900

over 2.25

Over 4.5

Over 11.2