Veris Industries H6812 SERIES Install User Manual
Notice, Danger, Installation guide

Z202815-0F
PAGE 1
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02111
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
POWER MONITORING
INSTALLATION GUIDE
Installer’s Specifications
Output at Rated Current
0.333 or 1 VAC
Accuracy
1% from 10% to 100% of rated current
Frequency Range
50/60 Hz
Leads
18AWG, 600VAC, UL 1015 twisted pair, 6 ft. (1.8m) standard length
Weight
H6810: 0.340 kg; H6811: 0.580 kg; H6812: 0.870 kg
Operating Temperature Range
-15° to 60°C (5° to 140°F)
Storage Temperature Range
-40° to 70°C (-40° to 158°F)
Humidity Range
0-95% noncondensing
Max. Voltage L-N Sensed Conductor
600VAC (basic insulation rating) *
Altitude of Operation
3km max.
Installation Category
Cat II or Cat III
* Do not apply 600V Class current transducers to circuits having a phase-to-phase voltage greater
than 600V, unless adequate additional insulation is applied between the primary conductor and
the current transducers. Veris assumes no responsibility for damage of equipment or personal
injury caused by products operated on circuits above their published ratings.
1 VAC and 0.333 VAC Current Transducers
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
• This product provides basic insulation only.
PRODUCT IDENTIFICATION
QUICK INSTALL
Installation must be performed by a qualified electrician.
Disconnect and lock out power to the primary circuit
before installing these current transducers (CTs).
1. Connect the transducer output leads to the meter inputs. The white wire is the X1
lead.
2. Depress the tabs on one end of the current transducer to open it and slip it over the
primary leads. Note labeling on product indicating “source side.”
3. Check the core ends on both sections of the CT to assure there is no rust or debris in
the closure areas.
4. Close and latch the CT, and mount it securely.
5. Reconnect power to the panel.
Optional mounting kit available. See Veris AH06.
H6810, H6811, H6812
H681
Model/Amps
Small:
0-100 = 100A
0-200 = 200A
0-300 = 300A
Medium:
1-400 = 400A
1-600 = 600A
1-800 = 800A
-
Output Type
1V = 0-1VAC
0.3V = 0-0.333VAC
Large:
2-800 = 800A
2-1200 = 1200A
2-1600 = 1600A
2-2000 = 2000A
2-2400 = 2400A
Documentation must be consulted where this symbol is used on the product.
This symbol indicates an electrical shock hazard exist.
Always use this product in the manner specified or the protection provided by the
product may be impaired. This product must be installed in an appropriate Fire and
Electrical enclosure per local regulations.