beautypg.com

Installation guide, Wiring & configuration, Jumper configuration – Veris Industries EP2 SERIES Install User Manual

Page 2: Options, Terminal block connections

background image

Z203044-0U

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

EP2

inStallation GUiDE

WirinG & confiGuration

Jumper Configuration

Input

Current (4-20 mA) or Voltage (0-5 V or 0-10 V)

Voltage

For voltage mode of operation, select 0-5 V or 0-10 V

Pressure Range

Select 0-20 psi or 3-15 psi scaling

Operation Mode

Select AUTO for normal operation or MANUAL to adjust pressure

using the pushbuttons

Options

Alarm Mode Relay

The alarm contacts open if the EP2 cannot obtain 80% of

commanded pressure within two (2) minutes

Manual Mode Alarm

Contacts open when manual mode is selected (auto mode contacts

are closed)

Vent On Power Fail

The EP2 vents the branch line pressure on power failure

Terminal Block Connections

GND/Common

Power supply ground and signal common.

Input Signal

4-20 mA, 0-10 VDC, or 0-5 VDC input from the control system.

Power

22-30 VDC, 20-30 VAC. From the control system or external power

supply or transformer.

Pressure Loss

Alarm (optional)

Normally closed, solid-state contacts open if the main supply pressure

fails or if the transducer is otherwise unable to produce the correct

branch pressure. Connect to the digital input of the control system for

alarm status indication. If commanded pressure does not reach 80%

within 2 minutes, the alarm contacts open.

• 0-20 psi alarm contact does not change state when the

commanded pressure is 4 psi or less

• 3-15 psi alarm contact does not change state when the

commanded pressure is 5.4 psi or less

NOTE: In 24 VAC transformer applications, one side of the transformer secondary is connected to
the signal common. Some control systems may require a dedicated power supply transformer or
isolation transformer.

ALARM

MODE

MANUAL ADJUST

ON

OFF

Aut

o

Mode

M

anual

0-20psi

3-15psi

0-5V

0-10V

Curr

ent

Voltage

GND/C

OM

INPUT SIGNAL

POWER

PRESSURE

RANGE

PRESSURE

LOSS

ALARM

(OPTIONAL)

OPERATION

MODE

INPUT

MODE

VOLTAGE

MODE

SLIDE

SWITCH
OPTION

AVAILABLE

GND INPUT POWE

R

DIGIT

AL IN

DIGITAL INPUT

(CONTACT CLOSURE)

ANALOG OUT (0-5/0-10, 4-20mA)
COMMON

20-45 PSI OUT
REGULATOR

DUCT

DAMPER

TO DAMPER

TRAP/FILTER

PRESSURE L

OSS ALARM

POWER SUPPLY

24VAC/DC

VERIS PS-24 Series

CONTROL PANEL

AIR COMPRESSOR

EP21XX

+

-