Installation guide, Operation, Wiring example wiring color codes – Veris Industries H280 Install User Manual
Page 2: Status output, Status output connections line connections, Power source

Z203739-0A
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
H280, H280NC
OPERATION
The H280 and H280NC load status switches monitor both voltage and current on
manually switched loads (e.g., lights/fans in bathrooms). This device provides status
monitoring for loads that are not, or cannot be, controlled by a building control
system. The H280 has a normally open (N.O.) output switch, while the H280NC is
normally closed (N.C.). Dual colored LEDs provide easy indication of output, with
green for normal output and red for alarm status. The H280 and H280NC require no
external power to generate the output.
WIRING EXAMPLE
WIRING COLOR CODES
Status Output
POWER
SOURCE
Swit
ch
Orange
Orange
(H280: Grey;
H280NC: Brown)
Neutral
Line
Wht/Yellow
Current
Switch
Voltage
Switch
Output
Neutral
ORANGE
White
ORANGE
yello
w
yello
w
From Line
To Load
Current Flow
110-277VAC
STATUS OUTPUT
VOLTAGE
CURRENT
H280
H280NC
LED
ON
ON
OPEN
CLOSED
GREEN
ON
OFF
CLOSED
OPEN
RED
OFF
OFF
OPEN
CLOSED
OFF
NOTE: Incidental loads as small as 30 mA AC connected in parallel to the sensed load (e.g. pilot
lamps or control circuits) might draw enough current to give a false load presence signal, even
though the true load has been interrupted.
GREY
COMMON
N.O.
GREY
H280 (N.O.)
H280NC (N.C.)
BROWN
COMMON
N.C.
BROWN
Status Output Connections
Line Connections