d. Measuring AC Amps
CAUTION!
Do not attempt to make a current measurement with the
test leads connected in parallel with circuit to be tested.
Test leads must be connected in series with the circuit.
WARNING!
Do not attempt to make a current measurement of
circuits with more than 600V present. Instrument
damage and /or personal injury may result.
Instrument set-up:
FUNCTION
BLACK RED
MINIMUM
MAXIMUM
TEST LEAD
TEST LEAD
READING
READING
µA
COM
mA
0.1µA
3000µA
mA
COM
mA
10µA
300mA
A
COM
A
1mA
10.00A
Measurement Procedure:
1.
Disconnect power to circuit to be measured.
2.
Plug black test lead into the COM input jack.
3.
Plug the red test lead into the mA or A input jack
depending on the value of current to be measured.
4.
Set the rotary switch to the µA, mA or A function.
5.
Push the F4 button
6.
Connect test leads in series to circuit to be measured.
7.
Reconnect power to circuit to be measured.
8.
Read the current on the 440.
!