Veris Industries VT7600H SERIES Datasheet User Manual
Communicating thermostats: heat pump control, Bacnet, echelon, & wireless models available, Vt7600h series

setp
oint de
vices
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Communicating Thermostats:
Heat Pump Control
SPECIFICATIONS
Thermostat Power Requirements
19-30VAC; 50 or 60 Hz; 2 VA Class 2
Operating Conditions
0° to 50°C (32° to 122°F); 0 to 95% RH non-condensing
Storage Conditions
-30° to 50°C (-22° to 122°F); 0 to 95% RH non-condensing
Temperature Sensor
Local 10 K NTC thermistor
Resolution
± 0.1°C (± 0.2°F)
Control Accuracy
Temp: ±0.5°C (±0.9°F ) @ 21°C (70°F) typical, calibrated
Occupied and Unoccupied Setpoint Range Cooling
12° to 38°C (54° to 100°F)
Occupied and Unoccupied Setpoint Range Heating
4.5° to 32°C (40° to 90°F)
Room and Outdoor Air Temperature Display
-40° to 50°C (-40° to 122°F)
Proportional Band for Room Temperature Range Control
Cooling & Heating: 1.8°C (3.2°F )
Binary Inputs
Dry contact across terminal BI1, BI2 & UI3 to Scom
Outputs Rating
Triac output: 30VAC, 1A max., 3A in-rush; Analog: 0 to 10VDC into 2kΩ resistance min.
Economizer Analog Output Rating
0 to 10VDC into 2kΩ resistance min.
Economizer Analog Output Accuracy
±3% typical
Wire Gauge
18 gauge maximum, 22 gauge recommended
Dimensions
4.94” x 3.38” x 1.13”
Approximate Shipping Weight
0.75 lb (0.34 kg)
UL: 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN , XAPX (US) and XAPX7 (Canada)
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
Industry Canada: ICES-003 (Canada)
CE: EMC Directive 89/336/EEC (European Union)
C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand); Supplier Code Number N10696
DESCRIPTION
The VT7600H PI thermostat family is designed for multi-stage control of heating/
cooling equipment such as heat pumps and self-contained units. The product
features an intuitive, menu-driven, back-lit LCD display which walks users through
the programming steps, making the process extremely simple.
All models contain two user-controlled digital inputs that monitor filter status,
change the occupancy status, and/or provide general purpose service indication.
Some models include up to three remote sensor inputs. All devices are available with
Echelon, BACnet, or wireless adapters.
APPLICATIONS
●
Single speed fans
●
Supply air temperature sensor
●
Outdoor air temperature sensor
●
Differential pressure switch
FEATURES
●
PI time proportioning algorithm...increased comfort, accuracy,
and energy savings
●
Smart fan...saves energy during night mode
●
Unique local configuration utility...minimizes parameter tampering
●
Lockable keypad...tamper proof, no need for thermostat guards
●
Freeze protection...prevents costly freeze damage
●
EEPROM memory...no loss of program
●
6 hour reserve time for clock...no need to reprogram day or time after
power outage
●
Auxiliary output...can be used for lighting and/or economizer override
●
Discharge air sensor...can be used to monitor unit efficiency
●
Low/High balance point...protect and optimize system performance
●
3 Heat/2 Cool...support single and two stages heat pump with one auxiliary
heat stage
BACnet, Echelon, & Wireless
Models Available
Year
Warranty
2
VT7600H5000
VT7600H SERIES