VTD2P-F50

INSTALLATION GUIDE

CONTACT AND COIL SPECIFICATIONS

Power Consumption

AC ...................................................... 2.5VA
DC...................................................... 2W

TYPICAL COIL PERFORMANCE

Resistive ...........12A@240VAC, 30VDC
Pilot Duty..........B300

CONTACT RATINGS

TIMING CHARACTERISTICS

Funtions Available

5

Time Ranges

0.1 sec

0-999

sec

0-999

0.1 min

0-999

min

0-999

0.1 hr

0-999

hr

0-999

10 hr

0-999

0.1 day

---

day

---

Tolerance

0%

(mechanical setting)

Repeatability

0.1%

Operate Time

(max)

25 msec

Reset Time

(max)

150 msec

Trigger Pulse Length

(min)

---

A-ON DELAY
B-REPEAT
C-INTERVAL
D-OFF DELAY
E-ONE SHOT

TIME

BASE

TIME

SET

LED
LAMP

A

S

0

0

0

.1S = 0.1-99.9
.1M = 0.1-99.9
.1H = 0.1-99.9
10H = 10-9,990 Hours

S = 1-999 SEC
M = 1-999 MIN
H = 1-999 HOURS

SELECT REQUIRED TIME
(SEE TIME RANGES ABOVE)

SET FUNCTIONS

A - ON DELAY

B - REPEAT

C - INTERVAL

D - OFF DELAY

E - ONE SHOT

TIME DELAY SETTINGS

TIME DELAY FUNCTIONS

ON DELAY: When input voltage is applied, the output relay remains off for a
programmed time interval, then turns on. Applying control input has no effect on
the timing or state of the relay. The LED flashes while the output relay is off and is on
continuously when the output relay is on.

OFF DELAY: Input voltage is on continuously. When control voltage is applied,
the output relay turns on. The time interval begins when the control input turns
off. Reapplying the control input resets the time to zero and inhibits timing until
removed. The LED is off while the control input is on, flashes during the time delay
interval, and is on continuously when the output relay is off.

REPEAT: Input voltage is on continuously. When input voltage is first applied, the
output relay remains off for a programmed time interval, then turns on. Relay stays
on for an equal time interval, then cycles on and off for this time interval until the
input power is removed. Applying control input has no effect on the timing or state of
the relay. The LED flashes when output relay is off and is on continuously when relay
is on.

INTERVAL: When input voltage is applied, the output relay turns on for a
programmed time interval. The output relay only turns on once for each application
of input voltage. Applying control input has no effect on the timing or state of the
relay. The LED flashes when the output relay is on and is on continuously when the
output relay is off.

ONE SHOT: Input voltage is on continuously. When the control voltage is applied, the
output relay turns on for a programmed time interval, then turns off. The LED is on
continuously when the output relay is off and flashes when the relay is on.

Function

Timing Chart

ON DELAY
(Power On)

OFF DELAY
(S Break)

REPEAT CYCLE
(Starting Off)

INTERVAL
(Power On)

ONE SHOT

R

U

T

T

S

R

U

T

T

R

U

T

T

T

T

T

T

R

U

T

T

T

S

R

U

T

T

T

T

T

U: Applied input voltage
S: Control switch (open or closed)
R: Relay contacts (on or off)
T: Time delay