Veris Industries H939 SERIES Datasheet User Manual
Status and control in one package, Typical coil performance, Relay contact ratings

current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Status And Control In One Package
Current Switches with Relay:
Adjustable Trip Point, High
Voltage Output
DESCRIPTION
Hawkeye Relay Combination Series high voltage output current switches are the
ideal solution for the automation installer. These units combine a current switch
and relay into a single package, reducing the space required for total control of fans
and pumps. The integrated current switch and relay operate independently of one
another. All relay connections are externally available for maximum flexibility.
These products perform the functions of start/stop and status monitoring with one
device instead of two.
APPLICATIONS
●
Starting/stopping and monitoring positive status of motors
●
Detecting belt loss and coupling shear
FEATURES
●
Combines command relay & fan/pump status sensor in a single, easy to
install unit
●
Reduces number of components installed...fits better in small starter enclosures
●
Command relay and status in a single unit
●
Easier to install than differential pressure switches...no additional wiring
needed
●
Detect belt loss and motor failure...ideal for fan and pump status
●
Bracket on H939, H949, and H959 can be installed in three different
configurations...added flexibility
●
H749 and H949 feature SPDT command relay...saves installation time
●
Reduced charges from electrician
●
Relay and status LEDs for easy setup
●
Polarity insensitive status output...fast trouble-free installation
●
Adjustable trip point for current sensor status...fits many applications
●
5-year warranty
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power
Induced from monitored conductor
Insulation Class
600VAC RMS
Frequency Range
50/60 Hz
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Hysteresis
10% Typical
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing
Do not use the LED status indicators as evidence of applied voltage.
Year
Warranty
5
Voltage
AC
DC
24V................................... 10mA
10mA
12V.................................................................... 20mA
TYPICAL COIL PERFORMANCE
Hx39, Hx59 (SPST, N.O.)
Resistive................................. 10A@250VAC, 30VDC
Inductive................................ 5A@250VAC, 30VDC
Hx49 (SPDT)
Resistive.............................. 8A@250VAC, 30VDC
Inductive............................. 3.5A@250VAC, 30VDC
RELAY CONTACT RATINGS
Pull In Voltage
Hx39 .............................................................. 20.1VDC
Hx49 .............................................................. 20.1VDC
Hx59 .............................................................. 8.4VDC
Drop Out Voltage
Hx39 .............................................................. 5.2VDC
Hx49 .............................................................. 5.2VDC
Hx59 .............................................................. 3.0VDC
H739
H939
H739 SERIES & H939 SERIES
TM
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
Calibrated
Trip Point
Off
Off
Fan/pump
On
Loss of Belt/Coupling Shear
Electrical
Failure
HQ0001761.C 01131